🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 1000 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.55%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.11V (4.21%)
Voltage at Load End233.9 VLoss: 6.13 V (2920.5 W)
Power & Breaker (125%)114.32 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1493.68 V (622.37%)0.0 V2463.88 V (1026.62%)711462.5 WDrop/Amp High
12 AWG3.31 mm²20 A938.63 V (391.1%)0.0 V1548.3 V (645.12%)447082.2 WDrop/Amp High
10 AWG5.26 mm²30 A590.66 V (246.11%)0.0 V974.31 V (405.96%)281338.8 WDrop/Amp High
8 AWG8.37 mm²50 A371.19 V (154.66%)0.0 V612.29 V (255.12%)176803.1 WDrop/Amp High
6 AWG13.3 mm²65 A233.6 V (97.33%)6.4 V385.33 V (160.55%)111266.3 WDrop/Amp High
4 AWG21.15 mm²85 A146.9 V (61.21%)93.1 V242.31 V (100.96%)69968.9 WDrop/Amp High
3 AWG26.67 mm²100 A116.49 V (48.54%)123.5 V192.16 V (80.07%)55487.1 WDrop/Amp High
2 AWG33.62 mm²115 A92.41 V (38.5%)147.6 V152.44 V (63.51%)44016.7 WDrop/Amp High
1 AWG42.41 mm²130 A73.26 V (30.52%)166.7 V120.84 V (50.35%)34893.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A58.08 V (24.2%)181.9 V95.81 V (39.92%)27665.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A46.08 V (19.2%)193.9 V76.0 V (31.67%)21946.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A36.55 V (15.23%)203.5 V60.29 V (25.12%)17407.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A28.98 V (12.08%)211.0 V47.81 V (19.92%)13804.5 WDrop/Amp High
250 kcmil126.7 mm²255 A24.52 V (10.22%)215.5 V40.45 V (16.85%)11679.9 WDrop/Amp High
300 kcmil152.0 mm²285 A20.44 V (8.52%)219.6 V33.72 V (14.05%)9735.8 WDrop/Amp High
350 kcmil177.3 mm²310 A17.52 V (7.3%)222.5 V28.91 V (12.04%)8346.5 WDrop/Amp High
400 kcmil202.7 mm²335 A15.33 V (6.39%)224.7 V25.28 V (10.53%)7300.7 WDrop/Amp High
500 kcmil253.4 mm²380 A12.26 V (5.11%)227.7 V20.22 V (8.43%)5839.9 WDrop/Amp High
600 kcmil304.0 mm²420 A10.22 V (4.26%)229.8 V16.86 V (7.02%)4867.9 W~ ≤5%
750 kcmil380.0 mm²475 A8.18 V (3.41%)231.8 V13.49 V (5.62%)3894.3 W~ ≤5%
1000 kcmil506.7 mm²545 A6.13 V (2.55%)233.9 V10.11 V (4.21%)2920.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 1000 feet one-way at 240V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 6.13V (2.55%) and delivers 233.9V at the load.

What size aluminum wire is required for 275 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.11V (4.21%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.