🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 300 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)6× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.5V (29.2%)
Voltage at Load End11.7 VLoss: 0.35 V (97.4 W)
Power & Breaker (125%)3.3 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 300 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A517.43 V (4311.89%)0.0 V853.51 V (7112.61%)142292.5 WDrop/Amp High
12 AWG3.31 mm²20 A325.15 V (2709.59%)0.0 V536.35 V (4469.56%)89416.4 WDrop/Amp High
10 AWG5.26 mm²30 A204.61 V (1705.08%)0.0 V337.51 V (2812.59%)56267.8 WDrop/Amp High
8 AWG8.37 mm²50 A128.58 V (1071.53%)0.0 V212.1 V (1767.53%)35360.6 WDrop/Amp High
6 AWG13.3 mm²65 A80.92 V (674.34%)0.0 V133.48 V (1112.35%)22253.3 WDrop/Amp High
4 AWG21.15 mm²85 A50.89 V (424.05%)0.0 V83.94 V (699.49%)13993.8 WDrop/Amp High
3 AWG26.67 mm²100 A40.35 V (336.29%)0.0 V66.57 V (554.71%)11097.4 WDrop/Amp High
2 AWG33.62 mm²115 A32.01 V (266.77%)0.0 V52.81 V (440.04%)8803.3 WDrop/Amp High
1 AWG42.41 mm²130 A25.38 V (211.48%)0.0 V41.86 V (348.84%)6978.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.12 V (167.67%)0.0 V33.19 V (276.58%)5533.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A15.96 V (133.01%)0.0 V26.33 V (219.4%)4389.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.66 V (105.5%)0.0 V20.88 V (174.03%)3481.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.04 V (83.66%)2.0 V16.56 V (138.01%)2760.9 WDrop/Amp High
250 kcmil126.7 mm²255 A8.49 V (70.79%)3.5 V14.01 V (116.77%)2336.0 WDrop/Amp High
300 kcmil152.0 mm²285 A7.08 V (59.0%)4.9 V11.68 V (97.33%)1947.2 WDrop/Amp High
350 kcmil177.3 mm²310 A6.07 V (50.59%)5.9 V10.01 V (83.44%)1669.3 WDrop/Amp High
400 kcmil202.7 mm²335 A5.31 V (44.25%)6.7 V8.76 V (72.99%)1460.1 WDrop/Amp High
500 kcmil253.4 mm²380 A4.25 V (35.39%)7.8 V7.01 V (58.38%)1168.0 WDrop/Amp High
600 kcmil304.0 mm²420 A3.54 V (29.5%)8.5 V5.84 V (48.67%)973.6 WDrop/Amp High
750 kcmil380.0 mm²475 A2.83 V (23.6%)9.2 V4.67 V (38.93%)778.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.12 V (17.7%)9.9 V3.5 V (29.2%)584.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 300 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 300 feet one-way at 12V (DC), you need 6× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.95%) and delivers 11.7V at the load.

What size aluminum wire is required for 275 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.5V (29.2%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.