⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

30 Amp Wire Size at 175 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 30 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.15%
Aluminum Wire (≤3% Drop)4 AWGDrop: 5.34V (2.23%)
Voltage at Load End234.9 VLoss: 5.15 V (154.5 W)
Power & Breaker (125%)7.2 kW40A Breaker Recommended

All AWG & kcmil Wire Gauges for 30 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A32.93 V (13.72%)207.1 V54.31 V (22.63%)987.8 WDrop/Amp High
12 AWG3.31 mm²20 A20.69 V (8.62%)219.3 V34.13 V (14.22%)620.7 WDrop/Amp High
10 AWG5.26 mm²30 A13.02 V (5.43%)227.0 V21.48 V (8.95%)390.6 WDrop/Amp High
8 AWG8.37 mm²50 A8.18 V (3.41%)231.8 V13.5 V (5.62%)245.5 W~ ≤5%
6 AWG13.3 mm²65 A5.15 V (2.15%)234.9 V8.49 V (3.54%)154.5 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A3.24 V (1.35%)236.8 V5.34 V (2.23%)97.1 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.57 V (1.07%)237.4 V4.24 V (1.76%)77.0 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.04 V (0.85%)238.0 V3.36 V (1.4%)61.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.61 V (0.67%)238.4 V2.66 V (1.11%)48.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.28 V (0.53%)238.7 V2.11 V (0.88%)38.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.02 V (0.42%)239.0 V1.68 V (0.7%)30.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.81 V (0.34%)239.2 V1.33 V (0.55%)24.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.64 V (0.27%)239.4 V1.05 V (0.44%)19.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.54 V (0.23%)239.5 V0.89 V (0.37%)16.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.45 V (0.19%)239.5 V0.74 V (0.31%)13.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.39 V (0.16%)239.6 V0.64 V (0.27%)11.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.34 V (0.14%)239.7 V0.56 V (0.23%)10.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.27 V (0.11%)239.7 V0.45 V (0.19%)8.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.23 V (0.09%)239.8 V0.37 V (0.15%)6.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.18 V (0.08%)239.8 V0.3 V (0.12%)5.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (0.06%)239.9 V0.22 V (0.09%)4.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 30 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 30A load over 175 feet one-way at 240V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 5.15V (2.15%) and delivers 234.9V at the load.

What size aluminum wire is required for 30 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 5.34V (2.23%).

What breaker size is needed for a 30A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (30A × 1.25 = 37.5A), which corresponds to a standard 40A circuit breaker.