⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

30 Amp Wire Size at 350 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 30 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.7%
Aluminum Wire (≤3% Drop)2 AWGDrop: 6.72V (2.8%)
Voltage at Load End233.5 VLoss: 6.48 V (194.3 W)
Power & Breaker (125%)7.2 kW40A Breaker Recommended

All AWG & kcmil Wire Gauges for 30 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A65.85 V (27.44%)174.1 V108.63 V (45.26%)1975.6 WDrop/Amp High
12 AWG3.31 mm²20 A41.38 V (17.24%)198.6 V68.26 V (28.44%)1241.5 WDrop/Amp High
10 AWG5.26 mm²30 A26.04 V (10.85%)214.0 V42.96 V (17.9%)781.2 WDrop/Amp High
8 AWG8.37 mm²50 A16.37 V (6.82%)223.6 V27.0 V (11.25%)491.0 WDrop/Amp High
6 AWG13.3 mm²65 A10.3 V (4.29%)229.7 V16.99 V (7.08%)309.0 W~ ≤5%
4 AWG21.15 mm²85 A6.48 V (2.7%)233.5 V10.68 V (4.45%)194.3 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A5.14 V (2.14%)234.9 V8.47 V (3.53%)154.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A4.07 V (1.7%)235.9 V6.72 V (2.8%)122.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.23 V (1.35%)236.8 V5.33 V (2.22%)96.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.56 V (1.07%)237.4 V4.22 V (1.76%)76.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.03 V (0.85%)238.0 V3.35 V (1.4%)60.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.61 V (0.67%)238.4 V2.66 V (1.11%)48.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.28 V (0.53%)238.7 V2.11 V (0.88%)38.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.08 V (0.45%)238.9 V1.78 V (0.74%)32.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.9 V (0.38%)239.1 V1.49 V (0.62%)27.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.77 V (0.32%)239.2 V1.27 V (0.53%)23.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.68 V (0.28%)239.3 V1.11 V (0.46%)20.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.54 V (0.23%)239.5 V0.89 V (0.37%)16.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.45 V (0.19%)239.5 V0.74 V (0.31%)13.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.36 V (0.15%)239.6 V0.59 V (0.25%)10.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.27 V (0.11%)239.7 V0.45 V (0.19%)8.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 30 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 30A load over 350 feet one-way at 240V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 6.48V (2.7%) and delivers 233.5V at the load.

What size aluminum wire is required for 30 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 6.72V (2.8%).

What breaker size is needed for a 30A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (30A × 1.25 = 37.5A), which corresponds to a standard 40A circuit breaker.