🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 350 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.8%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 6.19V (2.58%)
Voltage at Load End233.3 VLoss: 6.71 V (839.2 W)
Power & Breaker (125%)30.0 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A274.39 V (114.33%)0.0 V452.62 V (188.59%)34299.2 WDrop/Amp High
12 AWG3.31 mm²20 A172.43 V (71.85%)67.6 V284.43 V (118.51%)21553.5 WDrop/Amp High
10 AWG5.26 mm²30 A108.51 V (45.21%)131.5 V178.98 V (74.58%)13563.2 WDrop/Amp High
8 AWG8.37 mm²50 A68.19 V (28.41%)171.8 V112.48 V (46.87%)8523.6 WDrop/Amp High
6 AWG13.3 mm²65 A42.91 V (17.88%)197.1 V70.79 V (29.49%)5364.1 WDrop/Amp High
4 AWG21.15 mm²85 A26.99 V (11.24%)213.0 V44.51 V (18.55%)3373.2 WDrop/Amp High
3 AWG26.67 mm²100 A21.4 V (8.92%)218.6 V35.3 V (14.71%)2675.0 WDrop/Amp High
2 AWG33.62 mm²115 A16.98 V (7.07%)223.0 V28.0 V (11.67%)2122.0 WDrop/Amp High
1 AWG42.41 mm²130 A13.46 V (5.61%)226.5 V22.2 V (9.25%)1682.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.67 V (4.45%)229.3 V17.6 V (7.33%)1333.7 W~ ≤5%
2/0 AWG67.43 mm²175 A8.46 V (3.53%)231.5 V13.96 V (5.82%)1058.0 W~ ≤5%
3/0 AWG85.01 mm²200 A6.71 V (2.8%)233.3 V11.07 V (4.61%)839.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A5.32 V (2.22%)234.7 V8.78 V (3.66%)665.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.5 V (1.88%)235.5 V7.43 V (3.1%)563.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.75 V (1.56%)236.2 V6.19 V (2.58%)469.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.22 V (1.34%)236.8 V5.31 V (2.21%)402.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.82 V (1.17%)237.2 V4.64 V (1.94%)352.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.25 V (0.94%)237.7 V3.72 V (1.55%)281.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.88 V (0.78%)238.1 V3.1 V (1.29%)234.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.5 V (0.63%)238.5 V2.48 V (1.03%)187.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.13 V (0.47%)238.9 V1.86 V (0.77%)140.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 350 feet one-way at 240V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 6.71V (2.8%) and delivers 233.3V at the load.

What size aluminum wire is required for 125 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 6.19V (2.58%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.