🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

30 Amp Wire Size at 75 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 30 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 1.01%
Aluminum Wire (≤3% Drop)8 AWGDrop: 5.01V (1.04%)
Voltage at Load End475.2 VLoss: 4.83 V (251.1 W)
Power & Breaker (125%)24.94 kW40A Breaker Recommended

All AWG & kcmil Wire Gauges for 30 Amps at 75 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A12.22 V (2.55%)467.8 V20.16 V (4.2%)635.0 WDrop/Amp High
12 AWG3.31 mm²20 A7.68 V (1.6%)472.3 V12.67 V (2.64%)399.0 WDrop/Amp High
10 AWG5.26 mm²30 A4.83 V (1.01%)475.2 V7.97 V (1.66%)251.1 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A3.04 V (0.63%)477.0 V5.01 V (1.04%)157.8 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.91 V (0.4%)478.1 V3.15 V (0.66%)99.3 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.2 V (0.25%)478.8 V1.98 V (0.41%)62.5 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.95 V (0.2%)479.0 V1.57 V (0.33%)49.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.76 V (0.16%)479.2 V1.25 V (0.26%)39.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.6 V (0.12%)479.4 V0.99 V (0.21%)31.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.48 V (0.1%)479.5 V0.78 V (0.16%)24.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.38 V (0.08%)479.6 V0.62 V (0.13%)19.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.3 V (0.06%)479.7 V0.49 V (0.1%)15.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.24 V (0.05%)479.8 V0.39 V (0.08%)12.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.2 V (0.04%)479.8 V0.33 V (0.07%)10.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.17 V (0.03%)479.8 V0.28 V (0.06%)8.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.14 V (0.03%)479.9 V0.24 V (0.05%)7.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.13 V (0.03%)479.9 V0.21 V (0.04%)6.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.1 V (0.02%)479.9 V0.17 V (0.03%)5.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.08 V (0.02%)479.9 V0.14 V (0.03%)4.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.07 V (0.01%)479.9 V0.11 V (0.02%)3.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.01%)479.9 V0.08 V (0.02%)2.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 30 amps at 75 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 30A load over 75 feet one-way at 480V (3-Phase), you need 10 AWG copper wire. This produces a voltage drop of 4.83V (1.01%) and delivers 475.2V at the load.

What size aluminum wire is required for 30 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 5.01V (1.04%).

What breaker size is needed for a 30A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (30A × 1.25 = 37.5A), which corresponds to a standard 40A circuit breaker.