⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

30 Amp Wire Size at 30 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 30 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 0.4%
Aluminum Wire (≤3% Drop)8 AWGDrop: 2.0V (0.42%)
Voltage at Load End478.1 VLoss: 1.93 V (100.4 W)
Power & Breaker (125%)24.94 kW40A Breaker Recommended

All AWG & kcmil Wire Gauges for 30 Amps at 30 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4.89 V (1.02%)475.1 V8.06 V (1.68%)254.0 WDrop/Amp High
12 AWG3.31 mm²20 A3.07 V (0.64%)476.9 V5.07 V (1.06%)159.6 WDrop/Amp High
10 AWG5.26 mm²30 A1.93 V (0.4%)478.1 V3.19 V (0.66%)100.4 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A1.21 V (0.25%)478.8 V2.0 V (0.42%)63.1 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A0.76 V (0.16%)479.2 V1.26 V (0.26%)39.7 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.48 V (0.1%)479.5 V0.79 V (0.17%)25.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.38 V (0.08%)479.6 V0.63 V (0.13%)19.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.3 V (0.06%)479.7 V0.5 V (0.1%)15.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.24 V (0.05%)479.8 V0.4 V (0.08%)12.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.19 V (0.04%)479.8 V0.31 V (0.07%)9.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.15 V (0.03%)479.8 V0.25 V (0.05%)7.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.12 V (0.02%)479.9 V0.2 V (0.04%)6.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.09 V (0.02%)479.9 V0.16 V (0.03%)4.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.08 V (0.02%)479.9 V0.13 V (0.03%)4.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.07 V (0.01%)479.9 V0.11 V (0.02%)3.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.06 V (0.01%)479.9 V0.09 V (0.02%)3.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.05 V (0.01%)479.9 V0.08 V (0.02%)2.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.04 V (0.01%)480.0 V0.07 V (0.01%)2.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.03 V (0.01%)480.0 V0.06 V (0.01%)1.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.03 V (0.01%)480.0 V0.04 V (0.01%)1.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.02 V (0.0%)480.0 V0.03 V (0.01%)1.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 30 amps at 30 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 30A load over 30 feet one-way at 480V (3-Phase), you need 10 AWG copper wire. This produces a voltage drop of 1.93V (0.4%) and delivers 478.1V at the load.

What size aluminum wire is required for 30 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 2.0V (0.42%).

What breaker size is needed for a 30A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (30A × 1.25 = 37.5A), which corresponds to a standard 40A circuit breaker.