⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 75 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 0.67%
Aluminum Wire (≤3% Drop)2 AWGDrop: 3.33V (0.69%)
Voltage at Load End476.8 VLoss: 3.21 V (444.1 W)
Power & Breaker (125%)66.51 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 75 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A32.59 V (6.79%)447.4 V53.76 V (11.2%)4515.7 WDrop/Amp High
12 AWG3.31 mm²20 A20.48 V (4.27%)459.5 V33.78 V (7.04%)2837.7 WDrop/Amp High
10 AWG5.26 mm²30 A12.89 V (2.68%)467.1 V21.26 V (4.43%)1785.7 WDrop/Amp High
8 AWG8.37 mm²50 A8.1 V (1.69%)471.9 V13.36 V (2.78%)1122.2 WDrop/Amp High
6 AWG13.3 mm²65 A5.1 V (1.06%)474.9 V8.41 V (1.75%)706.2 WDrop/Amp High
4 AWG21.15 mm²85 A3.21 V (0.67%)476.8 V5.29 V (1.1%)444.1 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.54 V (0.53%)477.5 V4.19 V (0.87%)352.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.02 V (0.42%)478.0 V3.33 V (0.69%)279.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.6 V (0.33%)478.4 V2.64 V (0.55%)221.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.27 V (0.26%)478.7 V2.09 V (0.44%)175.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.01 V (0.21%)479.0 V1.66 V (0.35%)139.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.8 V (0.17%)479.2 V1.32 V (0.27%)110.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.63 V (0.13%)479.4 V1.04 V (0.22%)87.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.54 V (0.11%)479.5 V0.88 V (0.18%)74.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.45 V (0.09%)479.6 V0.74 V (0.15%)61.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.38 V (0.08%)479.6 V0.63 V (0.13%)53.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.33 V (0.07%)479.7 V0.55 V (0.11%)46.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.27 V (0.06%)479.7 V0.44 V (0.09%)37.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.22 V (0.05%)479.8 V0.37 V (0.08%)30.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.18 V (0.04%)479.8 V0.29 V (0.06%)24.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.13 V (0.03%)479.9 V0.22 V (0.05%)18.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 75 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 75 feet one-way at 480V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 3.21V (0.67%) and delivers 476.8V at the load.

What size aluminum wire is required for 80 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 3.33V (0.69%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.