🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 20 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 0.18%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 0.44V (0.21%)
Voltage at Load End207.6 VLoss: 0.38 V (198.7 W)
Power & Breaker (125%)108.08 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 20 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A32.59 V (15.67%)175.4 V53.76 V (25.84%)16934.0 WDrop/Amp High
12 AWG3.31 mm²20 A20.48 V (9.85%)187.5 V33.78 V (16.24%)10641.3 WDrop/Amp High
10 AWG5.26 mm²30 A12.89 V (6.2%)195.1 V21.26 V (10.22%)6696.3 WDrop/Amp High
8 AWG8.37 mm²50 A8.1 V (3.89%)199.9 V13.36 V (6.42%)4208.2 WDrop/Amp High
6 AWG13.3 mm²65 A5.1 V (2.45%)202.9 V8.41 V (4.04%)2648.3 WDrop/Amp High
4 AWG21.15 mm²85 A3.21 V (1.54%)204.8 V5.29 V (2.54%)1665.4 WDrop/Amp High
3 AWG26.67 mm²100 A2.54 V (1.22%)205.5 V4.19 V (2.02%)1320.7 WDrop/Amp High
2 AWG33.62 mm²115 A2.02 V (0.97%)206.0 V3.33 V (1.6%)1047.7 WDrop/Amp High
1 AWG42.41 mm²130 A1.6 V (0.77%)206.4 V2.64 V (1.27%)830.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.27 V (0.61%)206.7 V2.09 V (1.0%)658.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.01 V (0.48%)207.0 V1.66 V (0.8%)522.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.8 V (0.38%)207.2 V1.32 V (0.63%)414.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.63 V (0.3%)207.4 V1.04 V (0.5%)328.6 WDrop/Amp High
250 kcmil126.7 mm²255 A0.54 V (0.26%)207.5 V0.88 V (0.42%)278.0 WDrop/Amp High
300 kcmil152.0 mm²285 A0.45 V (0.21%)207.6 V0.74 V (0.35%)231.7 WDrop/Amp High
350 kcmil177.3 mm²310 A0.38 V (0.18%)207.6 V0.63 V (0.3%)198.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.33 V (0.16%)207.7 V0.55 V (0.27%)173.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.27 V (0.13%)207.7 V0.44 V (0.21%)139.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.22 V (0.11%)207.8 V0.37 V (0.18%)115.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.18 V (0.09%)207.8 V0.29 V (0.14%)92.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.13 V (0.06%)207.9 V0.22 V (0.11%)69.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 20 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 20 feet one-way at 208V (3-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 0.38V (0.18%) and delivers 207.6V at the load.

What size aluminum wire is required for 300 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 0.44V (0.21%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.