🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 80 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 0.74%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 1.77V (0.85%)
Voltage at Load End206.5 VLoss: 1.53 V (794.6 W)
Power & Breaker (125%)108.08 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 80 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A130.36 V (62.67%)77.6 V215.03 V (103.38%)67735.9 WDrop/Amp High
12 AWG3.31 mm²20 A81.92 V (39.38%)126.1 V135.12 V (64.96%)42565.2 WDrop/Amp High
10 AWG5.26 mm²30 A51.55 V (24.78%)156.5 V85.03 V (40.88%)26785.3 WDrop/Amp High
8 AWG8.37 mm²50 A32.39 V (15.57%)175.6 V53.44 V (25.69%)16832.8 WDrop/Amp High
6 AWG13.3 mm²65 A20.39 V (9.8%)187.6 V33.63 V (16.17%)10593.3 WDrop/Amp High
4 AWG21.15 mm²85 A12.82 V (6.16%)195.2 V21.15 V (10.17%)6661.5 WDrop/Amp High
3 AWG26.67 mm²100 A10.17 V (4.89%)197.8 V16.77 V (8.06%)5282.7 WDrop/Amp High
2 AWG33.62 mm²115 A8.06 V (3.88%)199.9 V13.3 V (6.4%)4190.7 WDrop/Amp High
1 AWG42.41 mm²130 A6.39 V (3.07%)201.6 V10.55 V (5.07%)3322.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.07 V (2.44%)202.9 V8.36 V (4.02%)2634.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.02 V (1.93%)204.0 V6.63 V (3.19%)2089.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.19 V (1.53%)204.8 V5.26 V (2.53%)1657.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.53 V (1.22%)205.5 V4.17 V (2.01%)1314.3 WDrop/Amp High
250 kcmil126.7 mm²255 A2.14 V (1.03%)205.9 V3.53 V (1.7%)1112.0 WDrop/Amp High
300 kcmil152.0 mm²285 A1.78 V (0.86%)206.2 V2.94 V (1.41%)926.9 WDrop/Amp High
350 kcmil177.3 mm²310 A1.53 V (0.74%)206.5 V2.52 V (1.21%)794.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.34 V (0.64%)206.7 V2.21 V (1.06%)695.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.07 V (0.51%)206.9 V1.77 V (0.85%)556.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.89 V (0.43%)207.1 V1.47 V (0.71%)463.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.71 V (0.34%)207.3 V1.18 V (0.57%)370.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.54 V (0.26%)207.5 V0.88 V (0.42%)278.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 80 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 80 feet one-way at 208V (3-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 1.53V (0.74%) and delivers 206.5V at the load.

What size aluminum wire is required for 300 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 1.77V (0.85%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.