🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 125 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 1.15%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 3.18V (1.33%)
Voltage at Load End237.2 VLoss: 2.76 V (827.8 W)
Power & Breaker (125%)72.0 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A235.19 V (98.0%)4.8 V387.96 V (161.65%)70558.3 WDrop/Amp High
12 AWG3.31 mm²20 A147.8 V (61.58%)92.2 V243.79 V (101.58%)44338.7 WDrop/Amp High
10 AWG5.26 mm²30 A93.0 V (38.75%)147.0 V153.41 V (63.92%)27901.4 WDrop/Amp High
8 AWG8.37 mm²50 A58.45 V (24.35%)181.6 V96.41 V (40.17%)17534.2 WDrop/Amp High
6 AWG13.3 mm²65 A36.78 V (15.33%)203.2 V60.67 V (25.28%)11034.7 WDrop/Amp High
4 AWG21.15 mm²85 A23.13 V (9.64%)216.9 V38.15 V (15.9%)6939.1 WDrop/Amp High
3 AWG26.67 mm²100 A18.34 V (7.64%)221.7 V30.26 V (12.61%)5502.9 WDrop/Amp High
2 AWG33.62 mm²115 A14.55 V (6.06%)225.4 V24.0 V (10.0%)4365.3 WDrop/Amp High
1 AWG42.41 mm²130 A11.54 V (4.81%)228.5 V19.03 V (7.93%)3460.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.15 V (3.81%)230.9 V15.09 V (6.29%)2743.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.25 V (3.02%)232.7 V11.97 V (4.99%)2176.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.75 V (2.4%)234.2 V9.49 V (3.96%)1726.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.56 V (1.9%)235.4 V7.53 V (3.14%)1369.0 WDrop/Amp High
250 kcmil126.7 mm²255 A3.86 V (1.61%)236.1 V6.37 V (2.65%)1158.3 WDrop/Amp High
300 kcmil152.0 mm²285 A3.22 V (1.34%)236.8 V5.31 V (2.21%)965.5 WDrop/Amp High
350 kcmil177.3 mm²310 A2.76 V (1.15%)237.2 V4.55 V (1.9%)827.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.41 V (1.01%)237.6 V3.98 V (1.66%)724.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.93 V (0.8%)238.1 V3.18 V (1.33%)579.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.61 V (0.67%)238.4 V2.65 V (1.11%)482.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.29 V (0.54%)238.7 V2.12 V (0.88%)386.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.97 V (0.4%)239.0 V1.59 V (0.66%)289.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 125 feet one-way at 240V (1-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 2.76V (1.15%) and delivers 237.2V at the load.

What size aluminum wire is required for 300 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 3.18V (1.33%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.