🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 120 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.18%
Aluminum Wire (≤3% Drop)8 AWGDrop: 9.35V (1.95%)
Voltage at Load End474.3 VLoss: 5.67 V (343.7 W)
Power & Breaker (125%)29.1 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 120 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A22.81 V (4.75%)457.2 V37.63 V (7.84%)1382.9 WDrop/Amp High
12 AWG3.31 mm²20 A14.34 V (2.99%)465.7 V23.65 V (4.93%)869.0 WDrop/Amp High
10 AWG5.26 mm²30 A9.02 V (1.88%)471.0 V14.88 V (3.1%)546.9 WDrop/Amp High
8 AWG8.37 mm²50 A5.67 V (1.18%)474.3 V9.35 V (1.95%)343.7 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A3.57 V (0.74%)476.4 V5.89 V (1.23%)216.3 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.24 V (0.47%)477.8 V3.7 V (0.77%)136.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.78 V (0.37%)478.2 V2.93 V (0.61%)107.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.41 V (0.29%)478.6 V2.33 V (0.49%)85.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.12 V (0.23%)478.9 V1.85 V (0.38%)67.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.89 V (0.18%)479.1 V1.46 V (0.3%)53.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.7 V (0.15%)479.3 V1.16 V (0.24%)42.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.56 V (0.12%)479.4 V0.92 V (0.19%)33.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.44 V (0.09%)479.6 V0.73 V (0.15%)26.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.37 V (0.08%)479.6 V0.62 V (0.13%)22.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.31 V (0.07%)479.7 V0.51 V (0.11%)18.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.27 V (0.06%)479.7 V0.44 V (0.09%)16.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.23 V (0.05%)479.8 V0.39 V (0.08%)14.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.19 V (0.04%)479.8 V0.31 V (0.06%)11.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.16 V (0.03%)479.8 V0.26 V (0.05%)9.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.12 V (0.03%)479.9 V0.21 V (0.04%)7.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.09 V (0.02%)479.9 V0.15 V (0.03%)5.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 120 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 120 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 5.67V (1.18%) and delivers 474.3V at the load.

What size aluminum wire is required for 35 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 9.35V (1.95%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.