⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 60 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 0.59%
Aluminum Wire (≤3% Drop)8 AWGDrop: 4.68V (0.97%)
Voltage at Load End477.2 VLoss: 2.83 V (171.8 W)
Power & Breaker (125%)29.1 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 60 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A11.41 V (2.38%)468.6 V18.82 V (3.92%)691.5 WDrop/Amp High
12 AWG3.31 mm²20 A7.17 V (1.49%)472.8 V11.82 V (2.46%)434.5 WDrop/Amp High
10 AWG5.26 mm²30 A4.51 V (0.94%)475.5 V7.44 V (1.55%)273.4 WDrop/Amp High
8 AWG8.37 mm²50 A2.83 V (0.59%)477.2 V4.68 V (0.97%)171.8 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.78 V (0.37%)478.2 V2.94 V (0.61%)108.1 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.12 V (0.23%)478.9 V1.85 V (0.39%)68.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.89 V (0.19%)479.1 V1.47 V (0.31%)53.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.71 V (0.15%)479.3 V1.16 V (0.24%)42.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.56 V (0.12%)479.4 V0.92 V (0.19%)33.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.44 V (0.09%)479.6 V0.73 V (0.15%)26.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.35 V (0.07%)479.6 V0.58 V (0.12%)21.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.28 V (0.06%)479.7 V0.46 V (0.1%)16.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.22 V (0.05%)479.8 V0.37 V (0.08%)13.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.19 V (0.04%)479.8 V0.31 V (0.06%)11.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.16 V (0.03%)479.8 V0.26 V (0.05%)9.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.13 V (0.03%)479.9 V0.22 V (0.05%)8.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.12 V (0.02%)479.9 V0.19 V (0.04%)7.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.09 V (0.02%)479.9 V0.15 V (0.03%)5.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.08 V (0.02%)479.9 V0.13 V (0.03%)4.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.06 V (0.01%)479.9 V0.1 V (0.02%)3.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.01%)480.0 V0.08 V (0.02%)2.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 60 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 60 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 2.83V (0.59%) and delivers 477.2V at the load.

What size aluminum wire is required for 35 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 4.68V (0.97%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.