🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 50 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.38%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 0.86V (0.41%)
Voltage at Load End207.2 VLoss: 0.78 V (473.0 W)
Power & Breaker (125%)126.09 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 50 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A95.05 V (45.7%)112.9 V156.79 V (75.38%)57622.6 WDrop/Amp High
12 AWG3.31 mm²20 A59.73 V (28.72%)148.3 V98.53 V (47.37%)36210.0 WDrop/Amp High
10 AWG5.26 mm²30 A37.59 V (18.07%)170.4 V62.0 V (29.81%)22786.1 WDrop/Amp High
8 AWG8.37 mm²50 A23.62 V (11.36%)184.4 V38.96 V (18.73%)14319.6 WDrop/Amp High
6 AWG13.3 mm²65 A14.87 V (7.15%)193.1 V24.52 V (11.79%)9011.7 WDrop/Amp High
4 AWG21.15 mm²85 A9.35 V (4.49%)198.7 V15.42 V (7.41%)5666.9 WDrop/Amp High
3 AWG26.67 mm²100 A7.41 V (3.56%)200.6 V12.23 V (5.88%)4494.0 WDrop/Amp High
2 AWG33.62 mm²115 A5.88 V (2.83%)202.1 V9.7 V (4.66%)3565.0 WDrop/Amp High
1 AWG42.41 mm²130 A4.66 V (2.24%)203.3 V7.69 V (3.7%)2826.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.7 V (1.78%)204.3 V6.1 V (2.93%)2240.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.93 V (1.41%)205.1 V4.84 V (2.33%)1777.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.33 V (1.12%)205.7 V3.84 V (1.84%)1409.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.84 V (0.89%)206.2 V3.04 V (1.46%)1118.1 WDrop/Amp High
250 kcmil126.7 mm²255 A1.56 V (0.75%)206.4 V2.57 V (1.24%)946.0 WDrop/Amp High
300 kcmil152.0 mm²285 A1.3 V (0.63%)206.7 V2.15 V (1.03%)788.5 WDrop/Amp High
350 kcmil177.3 mm²310 A1.12 V (0.54%)206.9 V1.84 V (0.88%)676.0 WDrop/Amp High
400 kcmil202.7 mm²335 A0.98 V (0.47%)207.0 V1.61 V (0.77%)591.3 WDrop/Amp High
500 kcmil253.4 mm²380 A0.78 V (0.38%)207.2 V1.29 V (0.62%)473.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.65 V (0.31%)207.3 V1.07 V (0.52%)394.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.52 V (0.25%)207.5 V0.86 V (0.41%)315.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.39 V (0.19%)207.6 V0.64 V (0.31%)236.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 50 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 50 feet one-way at 208V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 0.78V (0.38%) and delivers 207.2V at the load.

What size aluminum wire is required for 350 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 0.86V (0.41%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.