🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 500 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.71%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.44V (2.68%)
Voltage at Load End233.5 VLoss: 6.5 V (3942.6 W)
Power & Breaker (125%)145.49 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A950.53 V (396.05%)0.0 V1567.92 V (653.3%)576225.9 WDrop/Amp High
12 AWG3.31 mm²20 A597.31 V (248.88%)0.0 V985.28 V (410.53%)362099.6 WDrop/Amp High
10 AWG5.26 mm²30 A375.87 V (156.61%)0.0 V620.02 V (258.34%)227861.2 WDrop/Amp High
8 AWG8.37 mm²50 A236.21 V (98.42%)3.8 V389.64 V (162.35%)143195.9 WDrop/Amp High
6 AWG13.3 mm²65 A148.65 V (61.94%)91.3 V245.21 V (102.17%)90116.5 WDrop/Amp High
4 AWG21.15 mm²85 A93.48 V (38.95%)146.5 V154.2 V (64.25%)56669.0 WDrop/Amp High
3 AWG26.67 mm²100 A74.13 V (30.89%)165.9 V122.28 V (50.95%)44940.0 WDrop/Amp High
2 AWG33.62 mm²115 A58.81 V (24.5%)181.2 V97.0 V (40.42%)35649.9 WDrop/Amp High
1 AWG42.41 mm²130 A46.62 V (19.42%)193.4 V76.9 V (32.04%)28261.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A36.96 V (15.4%)203.0 V60.97 V (25.4%)22407.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A29.32 V (12.22%)210.7 V48.37 V (20.15%)17774.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A23.26 V (9.69%)216.7 V38.36 V (15.98%)14098.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A18.44 V (7.68%)221.6 V30.42 V (12.68%)11180.5 WDrop/Amp High
250 kcmil126.7 mm²255 A15.6 V (6.5%)224.4 V25.74 V (10.73%)9459.7 WDrop/Amp High
300 kcmil152.0 mm²285 A13.01 V (5.42%)227.0 V21.46 V (8.94%)7885.2 WDrop/Amp High
350 kcmil177.3 mm²310 A11.15 V (4.65%)228.8 V18.39 V (7.66%)6760.0 WDrop/Amp High
400 kcmil202.7 mm²335 A9.75 V (4.06%)230.2 V16.09 V (6.7%)5912.9 WDrop/Amp High
500 kcmil253.4 mm²380 A7.8 V (3.25%)232.2 V12.87 V (5.36%)4729.9 W~ ≤5%
600 kcmil304.0 mm²420 A6.5 V (2.71%)233.5 V10.73 V (4.47%)3942.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A5.2 V (2.17%)234.8 V8.58 V (3.58%)3154.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.9 V (1.63%)236.1 V6.44 V (2.68%)2365.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 500 feet one-way at 240V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 6.5V (2.71%) and delivers 233.5V at the load.

What size aluminum wire is required for 350 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.44V (2.68%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.