⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 600 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.25%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.72V (3.71%)
Voltage at Load End203.3 VLoss: 4.68 V (2838.5 W)
Power & Breaker (125%)126.09 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 600 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1140.63 V (548.38%)0.0 V1881.51 V (904.57%)691471.0 WDrop/Amp High
12 AWG3.31 mm²20 A716.77 V (344.6%)0.0 V1182.34 V (568.43%)434519.6 WDrop/Amp High
10 AWG5.26 mm²30 A451.05 V (216.85%)0.0 V744.02 V (357.7%)273433.4 WDrop/Amp High
8 AWG8.37 mm²50 A283.45 V (136.28%)0.0 V467.57 V (224.79%)171835.1 WDrop/Amp High
6 AWG13.3 mm²65 A178.38 V (85.76%)29.6 V294.25 V (141.47%)108139.8 WDrop/Amp High
4 AWG21.15 mm²85 A112.18 V (53.93%)95.8 V185.04 V (88.96%)68002.8 WDrop/Amp High
3 AWG26.67 mm²100 A88.96 V (42.77%)119.0 V146.74 V (70.55%)53928.0 WDrop/Amp High
2 AWG33.62 mm²115 A70.57 V (33.93%)137.4 V116.41 V (55.96%)42779.9 WDrop/Amp High
1 AWG42.41 mm²130 A55.94 V (26.9%)152.1 V92.28 V (44.36%)33913.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A44.35 V (21.32%)163.6 V73.16 V (35.17%)26888.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A35.18 V (16.92%)172.8 V58.04 V (27.9%)21329.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A27.91 V (13.42%)180.1 V46.04 V (22.13%)16918.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A22.13 V (10.64%)185.9 V36.51 V (17.55%)13416.6 WDrop/Amp High
250 kcmil126.7 mm²255 A18.73 V (9.0%)189.3 V30.89 V (14.85%)11351.7 WDrop/Amp High
300 kcmil152.0 mm²285 A15.61 V (7.5%)192.4 V25.75 V (12.38%)9462.2 WDrop/Amp High
350 kcmil177.3 mm²310 A13.38 V (6.43%)194.6 V22.07 V (10.61%)8112.0 WDrop/Amp High
400 kcmil202.7 mm²335 A11.7 V (5.63%)196.3 V19.31 V (9.28%)7095.5 WDrop/Amp High
500 kcmil253.4 mm²380 A9.36 V (4.5%)198.6 V15.44 V (7.43%)5675.8 W~ ≤5%
600 kcmil304.0 mm²420 A7.8 V (3.75%)200.2 V12.87 V (6.19%)4731.1 W~ ≤5%
750 kcmil380.0 mm²475 A6.24 V (3.0%)201.8 V10.3 V (4.95%)3784.9 W~ ≤5%
1000 kcmil506.7 mm²545 A4.68 V (2.25%)203.3 V7.72 V (3.71%)2838.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 600 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 600 feet one-way at 208V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 4.68V (2.25%) and delivers 203.3V at the load.

What size aluminum wire is required for 350 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.72V (3.71%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.