🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 750 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)19× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.96%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.15V (92.9%)
Voltage at Load End11.6 VLoss: 0.36 V (124.5 W)
Power & Breaker (125%)4.2 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 750 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1646.36 V (13719.66%)0.0 V2715.72 V (22631.03%)576225.9 WDrop/Amp High
12 AWG3.31 mm²20 A1034.57 V (8621.42%)0.0 V1706.56 V (14221.31%)362099.6 WDrop/Amp High
10 AWG5.26 mm²30 A651.03 V (5425.27%)0.0 V1073.9 V (8949.15%)227861.2 WDrop/Amp High
8 AWG8.37 mm²50 A409.13 V (3409.43%)0.0 V674.88 V (5623.96%)143195.9 WDrop/Amp High
6 AWG13.3 mm²65 A257.48 V (2145.63%)0.0 V424.71 V (3539.29%)90116.5 WDrop/Amp High
4 AWG21.15 mm²85 A161.91 V (1349.26%)0.0 V267.08 V (2225.65%)56669.0 WDrop/Amp High
3 AWG26.67 mm²100 A128.4 V (1070.0%)0.0 V211.8 V (1765.0%)44940.0 WDrop/Amp High
2 AWG33.62 mm²115 A101.86 V (848.81%)0.0 V168.02 V (1400.14%)35649.9 WDrop/Amp High
1 AWG42.41 mm²130 A80.75 V (672.88%)0.0 V133.19 V (1109.94%)28261.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A64.02 V (533.5%)0.0 V105.6 V (880.03%)22407.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A50.78 V (423.21%)0.0 V83.77 V (698.1%)17774.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A40.28 V (335.69%)0.0 V66.45 V (553.73%)14098.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A31.94 V (266.2%)0.0 V52.69 V (439.11%)11180.5 WDrop/Amp High
250 kcmil126.7 mm²255 A27.03 V (225.23%)0.0 V44.58 V (371.53%)9459.7 WDrop/Amp High
300 kcmil152.0 mm²285 A22.53 V (187.74%)0.0 V37.16 V (309.69%)7885.2 WDrop/Amp High
350 kcmil177.3 mm²310 A19.31 V (160.95%)0.0 V31.86 V (265.5%)6760.0 WDrop/Amp High
400 kcmil202.7 mm²335 A16.89 V (140.78%)0.0 V27.87 V (232.23%)5912.9 WDrop/Amp High
500 kcmil253.4 mm²380 A13.51 V (112.62%)0.0 V22.29 V (185.76%)4729.9 WDrop/Amp High
600 kcmil304.0 mm²420 A11.26 V (93.87%)0.7 V18.58 V (154.84%)3942.6 WDrop/Amp High
750 kcmil380.0 mm²475 A9.01 V (75.1%)3.0 V14.87 V (123.88%)3154.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.76 V (56.32%)5.2 V11.15 V (92.9%)2365.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 750 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 750 feet one-way at 12V (DC), you need 19× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.36V (2.96%) and delivers 11.6V at the load.

What size aluminum wire is required for 350 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.15V (92.9%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.