🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 750 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)22× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.93%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 12.74V (106.17%)
Voltage at Load End11.7 VLoss: 0.35 V (140.4 W)
Power & Breaker (125%)4.8 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 750 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1881.55 V (15679.62%)0.0 V3103.68 V (25864.04%)752621.5 WDrop/Amp High
12 AWG3.31 mm²20 A1182.37 V (9853.05%)0.0 V1950.35 V (16252.93%)472946.5 WDrop/Amp High
10 AWG5.26 mm²30 A744.04 V (6200.3%)0.0 V1227.31 V (10227.6%)297614.6 WDrop/Amp High
8 AWG8.37 mm²50 A467.58 V (3896.49%)0.0 V771.29 V (6427.38%)187031.4 WDrop/Amp High
6 AWG13.3 mm²65 A294.26 V (2452.15%)0.0 V485.39 V (4044.9%)117703.2 WDrop/Amp High
4 AWG21.15 mm²85 A185.04 V (1542.01%)0.0 V305.23 V (2543.6%)74016.7 WDrop/Amp High
3 AWG26.67 mm²100 A146.74 V (1222.86%)0.0 V242.06 V (2017.14%)58697.1 WDrop/Amp High
2 AWG33.62 mm²115 A116.41 V (970.07%)0.0 V192.02 V (1600.15%)46563.1 WDrop/Amp High
1 AWG42.41 mm²130 A92.28 V (769.01%)0.0 V152.22 V (1268.5%)36912.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A73.17 V (609.71%)0.0 V120.69 V (1005.74%)29266.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A58.04 V (483.67%)0.0 V95.74 V (797.82%)23216.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A46.04 V (383.64%)0.0 V75.94 V (632.83%)18414.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A36.51 V (304.23%)0.0 V60.22 V (501.84%)14603.1 WDrop/Amp High
250 kcmil126.7 mm²255 A30.89 V (257.41%)0.0 V50.95 V (424.6%)12355.6 WDrop/Amp High
300 kcmil152.0 mm²285 A25.75 V (214.56%)0.0 V42.47 V (353.93%)10299.0 WDrop/Amp High
350 kcmil177.3 mm²310 A22.07 V (183.95%)0.0 V36.41 V (303.42%)8829.4 WDrop/Amp High
400 kcmil202.7 mm²335 A19.31 V (160.9%)0.0 V31.85 V (265.4%)7723.0 WDrop/Amp High
500 kcmil253.4 mm²380 A15.44 V (128.7%)0.0 V25.48 V (212.3%)6177.8 WDrop/Amp High
600 kcmil304.0 mm²420 A12.87 V (107.28%)0.0 V21.24 V (176.96%)5149.5 WDrop/Amp High
750 kcmil380.0 mm²475 A10.3 V (85.83%)1.7 V16.99 V (141.57%)4119.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A7.72 V (64.36%)4.3 V12.74 V (106.17%)3089.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 750 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 750 feet one-way at 12V (DC), you need 22× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.93%) and delivers 11.7V at the load.

What size aluminum wire is required for 400 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 12.74V (106.17%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.