⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 750 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.15%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.27V (10.62%)
Voltage at Load End11.7 VLoss: 0.26 V (10.3 W)
Power & Breaker (125%)0.48 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 750 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A188.16 V (1567.96%)0.0 V310.37 V (2586.4%)7526.2 WDrop/Amp High
12 AWG3.31 mm²20 A118.24 V (985.31%)0.0 V195.04 V (1625.29%)4729.5 WDrop/Amp High
10 AWG5.26 mm²30 A74.4 V (620.03%)0.0 V122.73 V (1022.76%)2976.1 WDrop/Amp High
8 AWG8.37 mm²50 A46.76 V (389.65%)0.0 V77.13 V (642.74%)1870.3 WDrop/Amp High
6 AWG13.3 mm²65 A29.43 V (245.22%)0.0 V48.54 V (404.49%)1177.0 WDrop/Amp High
4 AWG21.15 mm²85 A18.5 V (154.2%)0.0 V30.52 V (254.36%)740.2 WDrop/Amp High
3 AWG26.67 mm²100 A14.67 V (122.29%)0.0 V24.21 V (201.71%)587.0 WDrop/Amp High
2 AWG33.62 mm²115 A11.64 V (97.01%)0.4 V19.2 V (160.02%)465.6 WDrop/Amp High
1 AWG42.41 mm²130 A9.23 V (76.9%)2.8 V15.22 V (126.85%)369.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.32 V (60.97%)4.7 V12.07 V (100.57%)292.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.8 V (48.37%)6.2 V9.57 V (79.78%)232.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.6 V (38.36%)7.4 V7.59 V (63.28%)184.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.65 V (30.42%)8.3 V6.02 V (50.18%)146.0 WDrop/Amp High
250 kcmil126.7 mm²255 A3.09 V (25.74%)8.9 V5.1 V (42.46%)123.6 WDrop/Amp High
300 kcmil152.0 mm²285 A2.57 V (21.46%)9.4 V4.25 V (35.39%)103.0 WDrop/Amp High
350 kcmil177.3 mm²310 A2.21 V (18.39%)9.8 V3.64 V (30.34%)88.3 WDrop/Amp High
400 kcmil202.7 mm²335 A1.93 V (16.09%)10.1 V3.18 V (26.54%)77.2 WDrop/Amp High
500 kcmil253.4 mm²380 A1.54 V (12.87%)10.5 V2.55 V (21.23%)61.8 WDrop/Amp High
600 kcmil304.0 mm²420 A1.29 V (10.73%)10.7 V2.12 V (17.7%)51.5 WDrop/Amp High
750 kcmil380.0 mm²475 A1.03 V (8.58%)11.0 V1.7 V (14.16%)41.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.77 V (6.44%)11.2 V1.27 V (10.62%)30.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 750 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 750 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.26V (2.15%) and delivers 11.7V at the load.

What size aluminum wire is required for 40 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.27V (10.62%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.