375 Amp Wire Size at 150 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 1.21%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 3.19V (1.33%)
Voltage at Load End237.1 VLoss: 2.9 V (1085.9 W)
Power & Breaker (125%)90.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A352.79 V (147.0%)0.0 V581.94 V (242.48%)132296.8 WDrop/Amp High
12 AWG3.31 mm²20 A221.69 V (92.37%)18.3 V365.69 V (152.37%)83135.1 WDrop/Amp High
10 AWG5.26 mm²30 A139.51 V (58.13%)100.5 V230.12 V (95.88%)52315.1 WDrop/Amp High
8 AWG8.37 mm²50 A87.67 V (36.53%)152.3 V144.62 V (60.26%)32876.6 WDrop/Amp High
6 AWG13.3 mm²65 A55.17 V (22.99%)184.8 V91.01 V (37.92%)20690.0 WDrop/Amp High
4 AWG21.15 mm²85 A34.7 V (14.46%)205.3 V57.23 V (23.85%)13010.7 WDrop/Amp High
3 AWG26.67 mm²100 A27.51 V (11.46%)212.5 V45.39 V (18.91%)10317.9 WDrop/Amp High
2 AWG33.62 mm²115 A21.83 V (9.09%)218.2 V36.0 V (15.0%)8184.9 WDrop/Amp High
1 AWG42.41 mm²130 A17.3 V (7.21%)222.7 V28.54 V (11.89%)6488.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.72 V (5.72%)226.3 V22.63 V (9.43%)5144.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.88 V (4.53%)229.1 V17.95 V (7.48%)4080.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.63 V (3.6%)231.4 V14.24 V (5.93%)3237.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.85 V (2.85%)233.2 V11.29 V (4.7%)2567.0 WDrop/Amp High
250 kcmil126.7 mm²255 A5.79 V (2.41%)234.2 V9.55 V (3.98%)2171.9 WDrop/Amp High
300 kcmil152.0 mm²285 A4.83 V (2.01%)235.2 V7.96 V (3.32%)1810.4 WDrop/Amp High
350 kcmil177.3 mm²310 A4.14 V (1.72%)235.9 V6.83 V (2.84%)1552.0 WDrop/Amp High
400 kcmil202.7 mm²335 A3.62 V (1.51%)236.4 V5.97 V (2.49%)1357.6 WDrop/Amp High
500 kcmil253.4 mm²380 A2.9 V (1.21%)237.1 V4.78 V (1.99%)1085.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.41 V (1.01%)237.6 V3.98 V (1.66%)905.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.93 V (0.8%)238.1 V3.19 V (1.33%)724.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.45 V (0.6%)238.6 V2.39 V (1.0%)543.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 150 feet one-way at 240V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 2.9V (1.21%) and delivers 237.1V at the load.

What size aluminum wire is required for 375 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 3.19V (1.33%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.