⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 75 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.6%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 1.59V (0.66%)
Voltage at Load End238.6 VLoss: 1.45 V (543.0 W)
Power & Breaker (125%)90.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A176.4 V (73.5%)63.6 V290.97 V (121.24%)66148.4 WDrop/Amp High
12 AWG3.31 mm²20 A110.85 V (46.19%)129.2 V182.85 V (76.19%)41567.6 WDrop/Amp High
10 AWG5.26 mm²30 A69.75 V (29.06%)170.2 V115.06 V (47.94%)26157.5 WDrop/Amp High
8 AWG8.37 mm²50 A43.84 V (18.26%)196.2 V72.31 V (30.13%)16438.3 WDrop/Amp High
6 AWG13.3 mm²65 A27.59 V (11.49%)212.4 V45.51 V (18.96%)10345.0 WDrop/Amp High
4 AWG21.15 mm²85 A17.35 V (7.23%)222.7 V28.62 V (11.92%)6505.4 WDrop/Amp High
3 AWG26.67 mm²100 A13.76 V (5.73%)226.2 V22.69 V (9.46%)5158.9 WDrop/Amp High
2 AWG33.62 mm²115 A10.91 V (4.55%)229.1 V18.0 V (7.5%)4092.5 WDrop/Amp High
1 AWG42.41 mm²130 A8.65 V (3.6%)231.3 V14.27 V (5.95%)3244.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.86 V (2.86%)233.1 V11.31 V (4.71%)2572.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.44 V (2.27%)234.6 V8.98 V (3.74%)2040.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.32 V (1.8%)235.7 V7.12 V (2.97%)1618.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.42 V (1.43%)236.6 V5.65 V (2.35%)1283.5 WDrop/Amp High
250 kcmil126.7 mm²255 A2.9 V (1.21%)237.1 V4.78 V (1.99%)1085.9 WDrop/Amp High
300 kcmil152.0 mm²285 A2.41 V (1.01%)237.6 V3.98 V (1.66%)905.2 WDrop/Amp High
350 kcmil177.3 mm²310 A2.07 V (0.86%)237.9 V3.41 V (1.42%)776.0 WDrop/Amp High
400 kcmil202.7 mm²335 A1.81 V (0.75%)238.2 V2.99 V (1.24%)678.8 WDrop/Amp High
500 kcmil253.4 mm²380 A1.45 V (0.6%)238.6 V2.39 V (1.0%)543.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.21 V (0.5%)238.8 V1.99 V (0.83%)452.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.97 V (0.4%)239.0 V1.59 V (0.66%)362.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.72 V (0.3%)239.3 V1.19 V (0.5%)271.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 75 feet one-way at 240V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 1.45V (0.6%) and delivers 238.6V at the load.

What size aluminum wire is required for 375 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 1.59V (0.66%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.