🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 125 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 1.01%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 2.65V (1.11%)
Voltage at Load End237.6 VLoss: 2.41 V (905.0 W)
Power & Breaker (125%)90.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A293.99 V (122.5%)0.0 V484.95 V (202.06%)110247.3 WDrop/Amp High
12 AWG3.31 mm²20 A184.74 V (76.98%)55.3 V304.74 V (126.98%)69279.3 WDrop/Amp High
10 AWG5.26 mm²30 A116.26 V (48.44%)123.7 V191.77 V (79.9%)43595.9 WDrop/Amp High
8 AWG8.37 mm²50 A73.06 V (30.44%)166.9 V120.51 V (50.21%)27397.2 WDrop/Amp High
6 AWG13.3 mm²65 A45.98 V (19.16%)194.0 V75.84 V (31.6%)17241.7 WDrop/Amp High
4 AWG21.15 mm²85 A28.91 V (12.05%)211.1 V47.69 V (19.87%)10842.3 WDrop/Amp High
3 AWG26.67 mm²100 A22.93 V (9.55%)217.1 V37.82 V (15.76%)8598.2 WDrop/Amp High
2 AWG33.62 mm²115 A18.19 V (7.58%)221.8 V30.0 V (12.5%)6820.8 WDrop/Amp High
1 AWG42.41 mm²130 A14.42 V (6.01%)225.6 V23.78 V (9.91%)5407.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.43 V (4.76%)228.6 V18.86 V (7.86%)4287.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.07 V (3.78%)230.9 V14.96 V (6.23%)3400.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.19 V (3.0%)232.8 V11.87 V (4.94%)2697.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.7 V (2.38%)234.3 V9.41 V (3.92%)2139.1 WDrop/Amp High
250 kcmil126.7 mm²255 A4.83 V (2.01%)235.2 V7.96 V (3.32%)1809.9 WDrop/Amp High
300 kcmil152.0 mm²285 A4.02 V (1.68%)236.0 V6.64 V (2.77%)1508.6 WDrop/Amp High
350 kcmil177.3 mm²310 A3.45 V (1.44%)236.6 V5.69 V (2.37%)1293.4 WDrop/Amp High
400 kcmil202.7 mm²335 A3.02 V (1.26%)237.0 V4.98 V (2.07%)1131.3 WDrop/Amp High
500 kcmil253.4 mm²380 A2.41 V (1.01%)237.6 V3.98 V (1.66%)905.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.01 V (0.84%)238.0 V3.32 V (1.38%)754.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.61 V (0.67%)238.4 V2.65 V (1.11%)603.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.21 V (0.5%)238.8 V1.99 V (0.83%)452.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 125 feet one-way at 240V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 2.41V (1.01%) and delivers 237.6V at the load.

What size aluminum wire is required for 375 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 2.65V (1.11%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.