🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 500 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.9V (2.87%)
Voltage at Load End233.0 VLoss: 6.97 V (4525.9 W)
Power & Breaker (125%)155.88 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1018.42 V (424.34%)0.0 V1679.92 V (699.97%)661483.8 WDrop/Amp High
12 AWG3.31 mm²20 A639.97 V (266.66%)0.0 V1055.66 V (439.86%)415675.6 WDrop/Amp High
10 AWG5.26 mm²30 A402.72 V (167.8%)0.0 V664.3 V (276.79%)261575.3 WDrop/Amp High
8 AWG8.37 mm²50 A253.08 V (105.45%)0.0 V417.47 V (173.95%)164383.1 WDrop/Amp High
6 AWG13.3 mm²65 A159.27 V (66.36%)80.7 V262.72 V (109.47%)103450.1 WDrop/Amp High
4 AWG21.15 mm²85 A100.16 V (41.73%)139.8 V165.21 V (68.84%)65053.7 WDrop/Amp High
3 AWG26.67 mm²100 A79.43 V (33.09%)160.6 V131.02 V (54.59%)51589.3 WDrop/Amp High
2 AWG33.62 mm²115 A63.01 V (26.25%)177.0 V103.93 V (43.31%)40924.6 WDrop/Amp High
1 AWG42.41 mm²130 A49.95 V (20.81%)190.1 V82.39 V (34.33%)32442.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A39.6 V (16.5%)200.4 V65.32 V (27.22%)25722.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A31.42 V (13.09%)208.6 V51.82 V (21.59%)20404.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A24.92 V (10.38%)215.1 V41.1 V (17.13%)16185.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A19.76 V (8.23%)220.2 V32.6 V (13.58%)12834.8 WDrop/Amp High
250 kcmil126.7 mm²255 A16.72 V (6.97%)223.3 V27.58 V (11.49%)10859.4 WDrop/Amp High
300 kcmil152.0 mm²285 A13.94 V (5.81%)226.1 V22.99 V (9.58%)9051.9 WDrop/Amp High
350 kcmil177.3 mm²310 A11.95 V (4.98%)228.1 V19.71 V (8.21%)7760.2 WDrop/Amp High
400 kcmil202.7 mm²335 A10.45 V (4.35%)229.5 V17.24 V (7.18%)6787.8 WDrop/Amp High
500 kcmil253.4 mm²380 A8.36 V (3.48%)231.6 V13.79 V (5.75%)5429.7 W~ ≤5%
600 kcmil304.0 mm²420 A6.97 V (2.9%)233.0 V11.49 V (4.79%)4525.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A5.57 V (2.32%)234.4 V9.2 V (3.83%)3620.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A4.18 V (1.74%)235.8 V6.9 V (2.87%)2715.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 500 feet one-way at 240V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 6.97V (2.9%) and delivers 233.0V at the load.

What size aluminum wire is required for 375 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.9V (2.87%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.