⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 75 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.95%
Aluminum Wire (≤3% Drop)6 AWGDrop: 4.85V (2.02%)
Voltage at Load End235.3 VLoss: 4.68 V (187.0 W)
Power & Breaker (125%)9.6 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A18.82 V (7.84%)221.2 V31.04 V (12.93%)752.6 WDrop/Amp High
12 AWG3.31 mm²20 A11.82 V (4.93%)228.2 V19.5 V (8.13%)472.9 WDrop/Amp High
10 AWG5.26 mm²30 A7.44 V (3.1%)232.6 V12.27 V (5.11%)297.6 WDrop/Amp High
8 AWG8.37 mm²50 A4.68 V (1.95%)235.3 V7.71 V (3.21%)187.0 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.94 V (1.23%)237.1 V4.85 V (2.02%)117.7 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.85 V (0.77%)238.1 V3.05 V (1.27%)74.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.47 V (0.61%)238.5 V2.42 V (1.01%)58.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.16 V (0.49%)238.8 V1.92 V (0.8%)46.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.92 V (0.38%)239.1 V1.52 V (0.63%)36.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.73 V (0.3%)239.3 V1.21 V (0.5%)29.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.58 V (0.24%)239.4 V0.96 V (0.4%)23.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.46 V (0.19%)239.5 V0.76 V (0.32%)18.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.37 V (0.15%)239.6 V0.6 V (0.25%)14.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.31 V (0.13%)239.7 V0.51 V (0.21%)12.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.26 V (0.11%)239.7 V0.42 V (0.18%)10.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.22 V (0.09%)239.8 V0.36 V (0.15%)8.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.19 V (0.08%)239.8 V0.32 V (0.13%)7.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.15 V (0.06%)239.8 V0.25 V (0.11%)6.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.13 V (0.05%)239.9 V0.21 V (0.09%)5.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.1 V (0.04%)239.9 V0.17 V (0.07%)4.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.03%)239.9 V0.13 V (0.05%)3.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 75 feet one-way at 240V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 4.68V (1.95%) and delivers 235.3V at the load.

What size aluminum wire is required for 40 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 4.85V (2.02%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.