🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 120 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 1.96%
Aluminum Wire (≤3% Drop)4 AWGDrop: 4.88V (2.03%)
Voltage at Load End235.3 VLoss: 4.71 V (188.3 W)
Power & Breaker (125%)9.6 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A30.1 V (12.54%)209.9 V49.66 V (20.69%)1204.2 WDrop/Amp High
12 AWG3.31 mm²20 A18.92 V (7.88%)221.1 V31.21 V (13.0%)756.7 WDrop/Amp High
10 AWG5.26 mm²30 A11.9 V (4.96%)228.1 V19.64 V (8.18%)476.2 WDrop/Amp High
8 AWG8.37 mm²50 A7.48 V (3.12%)232.5 V12.34 V (5.14%)299.3 W~ ≤5%
6 AWG13.3 mm²65 A4.71 V (1.96%)235.3 V7.77 V (3.24%)188.3 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.96 V (1.23%)237.0 V4.88 V (2.03%)118.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.35 V (0.98%)237.7 V3.87 V (1.61%)93.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.86 V (0.78%)238.1 V3.07 V (1.28%)74.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.48 V (0.62%)238.5 V2.44 V (1.01%)59.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.17 V (0.49%)238.8 V1.93 V (0.8%)46.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.93 V (0.39%)239.1 V1.53 V (0.64%)37.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.74 V (0.31%)239.3 V1.22 V (0.51%)29.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.58 V (0.24%)239.4 V0.96 V (0.4%)23.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.49 V (0.21%)239.5 V0.82 V (0.34%)19.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.41 V (0.17%)239.6 V0.68 V (0.28%)16.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.35 V (0.15%)239.6 V0.58 V (0.24%)14.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.31 V (0.13%)239.7 V0.51 V (0.21%)12.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.25 V (0.1%)239.8 V0.41 V (0.17%)9.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.21 V (0.09%)239.8 V0.34 V (0.14%)8.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.16 V (0.07%)239.8 V0.27 V (0.11%)6.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.12 V (0.05%)239.9 V0.2 V (0.08%)4.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 120 feet one-way at 240V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 4.71V (1.96%) and delivers 235.3V at the load.

What size aluminum wire is required for 40 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 4.88V (2.03%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.