🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 600 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 6.08V (2.53%)
Voltage at Load End234.1 VLoss: 5.85 V (234.1 W)
Power & Breaker (125%)9.6 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A150.52 V (62.72%)89.5 V248.29 V (103.46%)6021.0 WDrop/Amp High
12 AWG3.31 mm²20 A94.59 V (39.41%)145.4 V156.03 V (65.01%)3783.6 WDrop/Amp High
10 AWG5.26 mm²30 A59.52 V (24.8%)180.5 V98.19 V (40.91%)2380.9 WDrop/Amp High
8 AWG8.37 mm²50 A37.41 V (15.59%)202.6 V61.7 V (25.71%)1496.3 WDrop/Amp High
6 AWG13.3 mm²65 A23.54 V (9.81%)216.5 V38.83 V (16.18%)941.6 WDrop/Amp High
4 AWG21.15 mm²85 A14.8 V (6.17%)225.2 V24.42 V (10.17%)592.1 WDrop/Amp High
3 AWG26.67 mm²100 A11.74 V (4.89%)228.3 V19.36 V (8.07%)469.6 W~ ≤5%
2 AWG33.62 mm²115 A9.31 V (3.88%)230.7 V15.36 V (6.4%)372.5 W~ ≤5%
1 AWG42.41 mm²130 A7.38 V (3.08%)232.6 V12.18 V (5.07%)295.3 W~ ≤5%
1/0 AWG53.49 mm²150 A5.85 V (2.44%)234.1 V9.66 V (4.02%)234.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A4.64 V (1.93%)235.4 V7.66 V (3.19%)185.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.68 V (1.53%)236.3 V6.08 V (2.53%)147.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.92 V (1.22%)237.1 V4.82 V (2.01%)116.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.47 V (1.03%)237.5 V4.08 V (1.7%)98.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.06 V (0.86%)237.9 V3.4 V (1.42%)82.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.77 V (0.74%)238.2 V2.91 V (1.21%)70.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.54 V (0.64%)238.5 V2.55 V (1.06%)61.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.24 V (0.51%)238.8 V2.04 V (0.85%)49.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.03 V (0.43%)239.0 V1.7 V (0.71%)41.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.82 V (0.34%)239.2 V1.36 V (0.57%)33.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.62 V (0.26%)239.4 V1.02 V (0.42%)24.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 600 feet one-way at 240V (1-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 5.85V (2.44%) and delivers 234.1V at the load.

What size aluminum wire is required for 40 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 6.08V (2.53%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.