80 Amp Wire Size at 600 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.43%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 6.8V (2.83%)
Voltage at Load End234.2 VLoss: 5.84 V (467.3 W)
Power & Breaker (125%)19.2 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A301.05 V (125.44%)0.0 V496.59 V (206.91%)24083.9 WDrop/Amp High
12 AWG3.31 mm²20 A189.18 V (78.82%)50.8 V312.06 V (130.02%)15134.3 WDrop/Amp High
10 AWG5.26 mm²30 A119.05 V (49.6%)121.0 V196.37 V (81.82%)9523.7 WDrop/Amp High
8 AWG8.37 mm²50 A74.81 V (31.17%)165.2 V123.41 V (51.42%)5985.0 WDrop/Amp High
6 AWG13.3 mm²65 A47.08 V (19.62%)192.9 V77.66 V (32.36%)3766.5 WDrop/Amp High
4 AWG21.15 mm²85 A29.61 V (12.34%)210.4 V48.84 V (20.35%)2368.5 WDrop/Amp High
3 AWG26.67 mm²100 A23.48 V (9.78%)216.5 V38.73 V (16.14%)1878.3 WDrop/Amp High
2 AWG33.62 mm²115 A18.63 V (7.76%)221.4 V30.72 V (12.8%)1490.0 WDrop/Amp High
1 AWG42.41 mm²130 A14.76 V (6.15%)225.2 V24.36 V (10.15%)1181.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.71 V (4.88%)228.3 V19.31 V (8.05%)936.5 W~ ≤5%
2/0 AWG67.43 mm²175 A9.29 V (3.87%)230.7 V15.32 V (6.38%)742.9 W~ ≤5%
3/0 AWG85.01 mm²200 A7.37 V (3.07%)232.6 V12.15 V (5.06%)589.3 W~ ≤5%
4/0 AWG107.2 mm²230 A5.84 V (2.43%)234.2 V9.64 V (4.01%)467.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.94 V (2.06%)235.1 V8.15 V (3.4%)395.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.12 V (1.72%)235.9 V6.8 V (2.83%)329.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.53 V (1.47%)236.5 V5.83 V (2.43%)282.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.09 V (1.29%)236.9 V5.1 V (2.12%)247.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.47 V (1.03%)237.5 V4.08 V (1.7%)197.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.06 V (0.86%)237.9 V3.4 V (1.42%)164.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.65 V (0.69%)238.4 V2.72 V (1.13%)131.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.24 V (0.51%)238.8 V2.04 V (0.85%)98.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 600 feet one-way at 240V (1-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 5.84V (2.43%) and delivers 234.2V at the load.

What size aluminum wire is required for 80 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 6.8V (2.83%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.