⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

50 Amp Wire Size at 75 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 50 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)6 AWGDrop: 6.07V (2.53%)
Voltage at Load End234.2 VLoss: 5.84 V (292.2 W)
Power & Breaker (125%)12.0 kW63A Breaker Recommended

All AWG & kcmil Wire Gauges for 50 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A23.52 V (9.8%)216.5 V38.8 V (16.17%)1176.0 WDrop/Amp High
12 AWG3.31 mm²20 A14.78 V (6.16%)225.2 V24.38 V (10.16%)739.0 WDrop/Amp High
10 AWG5.26 mm²30 A9.3 V (3.88%)230.7 V15.34 V (6.39%)465.0 WDrop/Amp High
8 AWG8.37 mm²50 A5.84 V (2.44%)234.2 V9.64 V (4.02%)292.2 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A3.68 V (1.53%)236.3 V6.07 V (2.53%)183.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.31 V (0.96%)237.7 V3.82 V (1.59%)115.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.83 V (0.76%)238.2 V3.03 V (1.26%)91.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.46 V (0.61%)238.5 V2.4 V (1.0%)72.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.15 V (0.48%)238.8 V1.9 V (0.79%)57.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.91 V (0.38%)239.1 V1.51 V (0.63%)45.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.73 V (0.3%)239.3 V1.2 V (0.5%)36.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.58 V (0.24%)239.4 V0.95 V (0.4%)28.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.46 V (0.19%)239.5 V0.75 V (0.31%)22.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.39 V (0.16%)239.6 V0.64 V (0.27%)19.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.32 V (0.13%)239.7 V0.53 V (0.22%)16.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.28 V (0.11%)239.7 V0.46 V (0.19%)13.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.24 V (0.1%)239.8 V0.4 V (0.17%)12.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.19 V (0.08%)239.8 V0.32 V (0.13%)9.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.16 V (0.07%)239.8 V0.27 V (0.11%)8.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.13 V (0.05%)239.9 V0.21 V (0.09%)6.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.1 V (0.04%)239.9 V0.16 V (0.07%)4.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 50 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 50A load over 75 feet one-way at 240V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 5.84V (2.44%) and delivers 234.2V at the load.

What size aluminum wire is required for 50 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 6.07V (2.53%).

What breaker size is needed for a 50A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (50A × 1.25 = 62.5A), which corresponds to a standard 63A circuit breaker.