🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 80 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 0.5%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.18V (0.49%)
Voltage at Load End238.8 VLoss: 1.19 V (823.9 W)
Power & Breaker (125%)166.28 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A173.81 V (72.42%)66.2 V286.71 V (119.46%)120419.4 WDrop/Amp High
12 AWG3.31 mm²20 A109.22 V (45.51%)130.8 V180.17 V (75.07%)75671.4 WDrop/Amp High
10 AWG5.26 mm²30 A68.73 V (28.64%)171.3 V113.37 V (47.24%)47618.3 WDrop/Amp High
8 AWG8.37 mm²50 A43.19 V (18.0%)196.8 V71.25 V (29.69%)29925.0 WDrop/Amp High
6 AWG13.3 mm²65 A27.18 V (11.33%)212.8 V44.84 V (18.68%)18832.5 WDrop/Amp High
4 AWG21.15 mm²85 A17.09 V (7.12%)222.9 V28.2 V (11.75%)11842.7 WDrop/Amp High
3 AWG26.67 mm²100 A13.56 V (5.65%)226.4 V22.36 V (9.32%)9391.5 WDrop/Amp High
2 AWG33.62 mm²115 A10.75 V (4.48%)229.2 V17.74 V (7.39%)7450.1 WDrop/Amp High
1 AWG42.41 mm²130 A8.52 V (3.55%)231.5 V14.06 V (5.86%)5906.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.76 V (2.82%)233.2 V11.15 V (4.65%)4682.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.36 V (2.23%)234.6 V8.84 V (3.68%)3714.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.25 V (1.77%)235.7 V7.02 V (2.92%)2946.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.37 V (1.41%)236.6 V5.56 V (2.32%)2336.5 WDrop/Amp High
250 kcmil126.7 mm²255 A2.85 V (1.19%)237.1 V4.71 V (1.96%)1976.9 WDrop/Amp High
300 kcmil152.0 mm²285 A2.38 V (0.99%)237.6 V3.92 V (1.63%)1647.8 WDrop/Amp High
350 kcmil177.3 mm²310 A2.04 V (0.85%)238.0 V3.36 V (1.4%)1412.7 WDrop/Amp High
400 kcmil202.7 mm²335 A1.78 V (0.74%)238.2 V2.94 V (1.23%)1235.7 WDrop/Amp High
500 kcmil253.4 mm²380 A1.43 V (0.59%)238.6 V2.35 V (0.98%)988.4 WDrop/Amp High
600 kcmil304.0 mm²420 A1.19 V (0.5%)238.8 V1.96 V (0.82%)823.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.95 V (0.4%)239.0 V1.57 V (0.65%)659.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.71 V (0.3%)239.3 V1.18 V (0.49%)494.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 80 feet one-way at 240V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 1.19V (0.5%) and delivers 238.8V at the load.

What size aluminum wire is required for 400 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.18V (0.49%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.