⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 300 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.14%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.41V (2.12%)
Voltage at Load End203.5 VLoss: 4.46 V (3089.7 W)
Power & Breaker (125%)144.11 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 300 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A651.79 V (313.36%)0.0 V1075.15 V (516.9%)451572.9 WDrop/Amp High
12 AWG3.31 mm²20 A409.58 V (196.92%)0.0 V675.62 V (324.82%)283767.9 WDrop/Amp High
10 AWG5.26 mm²30 A257.74 V (123.91%)0.0 V425.15 V (204.4%)178568.8 WDrop/Amp High
8 AWG8.37 mm²50 A161.97 V (77.87%)46.0 V267.18 V (128.45%)112218.8 WDrop/Amp High
6 AWG13.3 mm²65 A101.93 V (49.01%)106.1 V168.14 V (80.84%)70621.9 WDrop/Amp High
4 AWG21.15 mm²85 A64.1 V (30.82%)143.9 V105.74 V (50.83%)44410.0 WDrop/Amp High
3 AWG26.67 mm²100 A50.83 V (24.44%)157.2 V83.85 V (40.31%)35218.3 WDrop/Amp High
2 AWG33.62 mm²115 A40.32 V (19.39%)167.7 V66.52 V (31.98%)27937.9 WDrop/Amp High
1 AWG42.41 mm²130 A31.97 V (15.37%)176.0 V52.73 V (25.35%)22147.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.35 V (12.19%)182.7 V41.81 V (20.1%)17559.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.11 V (9.67%)187.9 V33.16 V (15.94%)13929.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.95 V (7.67%)192.1 V26.31 V (12.65%)11049.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.65 V (6.08%)195.4 V20.86 V (10.03%)8761.9 WDrop/Amp High
250 kcmil126.7 mm²255 A10.7 V (5.14%)197.3 V17.65 V (8.49%)7413.4 WDrop/Amp High
300 kcmil152.0 mm²285 A8.92 V (4.29%)199.1 V14.71 V (7.07%)6179.4 WDrop/Amp High
350 kcmil177.3 mm²310 A7.65 V (3.68%)200.4 V12.61 V (6.06%)5297.6 WDrop/Amp High
400 kcmil202.7 mm²335 A6.69 V (3.22%)201.3 V11.03 V (5.3%)4633.8 WDrop/Amp High
500 kcmil253.4 mm²380 A5.35 V (2.57%)202.6 V8.83 V (4.24%)3706.7 WDrop/Amp High
600 kcmil304.0 mm²420 A4.46 V (2.14%)203.5 V7.36 V (3.54%)3089.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.57 V (1.72%)204.4 V5.89 V (2.83%)2471.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.68 V (1.29%)205.3 V4.41 V (2.12%)1853.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 300 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 300 feet one-way at 208V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 4.46V (2.14%) and delivers 203.5V at the load.

What size aluminum wire is required for 400 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.41V (2.12%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.