⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 300 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 2.76%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 5.52V (2.65%)
Voltage at Load End202.3 VLoss: 5.73 V (2979.9 W)
Power & Breaker (125%)108.08 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 300 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A488.84 V (235.02%)0.0 V806.36 V (387.67%)254009.8 WDrop/Amp High
12 AWG3.31 mm²20 A307.19 V (147.69%)0.0 V506.72 V (243.61%)159619.4 WDrop/Amp High
10 AWG5.26 mm²30 A193.31 V (92.94%)14.7 V318.87 V (153.3%)100444.9 WDrop/Amp High
8 AWG8.37 mm²50 A121.48 V (58.4%)86.5 V200.39 V (96.34%)63123.1 WDrop/Amp High
6 AWG13.3 mm²65 A76.45 V (36.76%)131.5 V126.11 V (60.63%)39724.8 WDrop/Amp High
4 AWG21.15 mm²85 A48.08 V (23.11%)159.9 V79.3 V (38.13%)24980.6 WDrop/Amp High
3 AWG26.67 mm²100 A38.12 V (18.33%)169.9 V62.89 V (30.23%)19810.3 WDrop/Amp High
2 AWG33.62 mm²115 A30.24 V (14.54%)177.8 V49.89 V (23.98%)15715.1 WDrop/Amp High
1 AWG42.41 mm²130 A23.98 V (11.53%)184.0 V39.55 V (19.01%)12457.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A19.01 V (9.14%)189.0 V31.36 V (15.07%)9877.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A15.08 V (7.25%)192.9 V24.87 V (11.96%)7835.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.96 V (5.75%)196.0 V19.73 V (9.49%)6215.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.48 V (4.56%)198.5 V15.65 V (7.52%)4928.5 WDrop/Amp High
250 kcmil126.7 mm²255 A8.03 V (3.86%)200.0 V13.24 V (6.36%)4170.0 WDrop/Amp High
300 kcmil152.0 mm²285 A6.69 V (3.22%)201.3 V11.03 V (5.31%)3475.9 WDrop/Amp High
350 kcmil177.3 mm²310 A5.73 V (2.76%)202.3 V9.46 V (4.55%)2979.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A5.02 V (2.41%)203.0 V8.27 V (3.98%)2606.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A4.01 V (1.93%)204.0 V6.62 V (3.18%)2085.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.34 V (1.61%)204.7 V5.52 V (2.65%)1738.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.68 V (1.29%)205.3 V4.41 V (2.12%)1390.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.01 V (0.96%)206.0 V3.31 V (1.59%)1042.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 300 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 300 feet one-way at 208V (3-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 5.73V (2.76%) and delivers 202.3V at the load.

What size aluminum wire is required for 300 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 5.52V (2.65%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.