45 Amp Wire Size at 175 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.33V (2.79%)
Voltage at Load End11.7 VLoss: 0.34 V (15.2 W)
Power & Breaker (125%)0.54 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 175 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A49.39 V (411.59%)0.0 V81.47 V (678.93%)2222.6 WDrop/Amp High
12 AWG3.31 mm²20 A31.04 V (258.64%)0.0 V51.2 V (426.64%)1396.7 WDrop/Amp High
10 AWG5.26 mm²30 A19.53 V (162.76%)0.0 V32.22 V (268.47%)878.9 WDrop/Amp High
8 AWG8.37 mm²50 A12.27 V (102.28%)0.0 V20.25 V (168.72%)552.3 WDrop/Amp High
6 AWG13.3 mm²65 A7.72 V (64.37%)4.3 V12.74 V (106.18%)347.6 WDrop/Amp High
4 AWG21.15 mm²85 A4.86 V (40.48%)7.1 V8.01 V (66.77%)218.6 WDrop/Amp High
3 AWG26.67 mm²100 A3.85 V (32.1%)8.1 V6.35 V (52.95%)173.3 WDrop/Amp High
2 AWG33.62 mm²115 A3.06 V (25.46%)8.9 V5.04 V (42.0%)137.5 WDrop/Amp High
1 AWG42.41 mm²130 A2.42 V (20.19%)9.6 V4.0 V (33.3%)109.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.92 V (16.0%)10.1 V3.17 V (26.4%)86.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.52 V (12.7%)10.5 V2.51 V (20.94%)68.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.21 V (10.07%)10.8 V1.99 V (16.61%)54.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.96 V (7.99%)11.0 V1.58 V (13.17%)43.1 WDrop/Amp High
250 kcmil126.7 mm²255 A0.81 V (6.76%)11.2 V1.34 V (11.15%)36.5 WDrop/Amp High
300 kcmil152.0 mm²285 A0.68 V (5.63%)11.3 V1.11 V (9.29%)30.4 WDrop/Amp High
350 kcmil177.3 mm²310 A0.58 V (4.83%)11.4 V0.96 V (7.96%)26.1 W~ ≤5%
400 kcmil202.7 mm²335 A0.51 V (4.22%)11.5 V0.84 V (6.97%)22.8 W~ ≤5%
500 kcmil253.4 mm²380 A0.41 V (3.38%)11.6 V0.67 V (5.57%)18.2 W~ ≤5%
600 kcmil304.0 mm²420 A0.34 V (2.82%)11.7 V0.56 V (4.65%)15.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.27 V (2.25%)11.7 V0.45 V (3.72%)12.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.2 V (1.69%)11.8 V0.33 V (2.79%)9.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 175 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 175 feet one-way at 12V (DC), you need 600 kcmil copper wire. This produces a voltage drop of 0.34V (2.82%) and delivers 11.7V at the load.

What size aluminum wire is required for 45 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.33V (2.79%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.