⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 120 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 0.31V (2.55%)
Voltage at Load End11.7 VLoss: 0.35 V (15.6 W)
Power & Breaker (125%)0.54 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 120 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A33.87 V (282.23%)0.0 V55.87 V (465.55%)1524.1 WDrop/Amp High
12 AWG3.31 mm²20 A21.28 V (177.35%)0.0 V35.11 V (292.55%)957.7 WDrop/Amp High
10 AWG5.26 mm²30 A13.39 V (111.61%)0.0 V22.09 V (184.1%)602.7 WDrop/Amp High
8 AWG8.37 mm²50 A8.42 V (70.14%)3.6 V13.88 V (115.69%)378.7 WDrop/Amp High
6 AWG13.3 mm²65 A5.3 V (44.14%)6.7 V8.74 V (72.81%)238.3 WDrop/Amp High
4 AWG21.15 mm²85 A3.33 V (27.76%)8.7 V5.49 V (45.78%)149.9 WDrop/Amp High
3 AWG26.67 mm²100 A2.64 V (22.01%)9.4 V4.36 V (36.31%)118.9 WDrop/Amp High
2 AWG33.62 mm²115 A2.1 V (17.46%)9.9 V3.46 V (28.8%)94.3 WDrop/Amp High
1 AWG42.41 mm²130 A1.66 V (13.84%)10.3 V2.74 V (22.83%)74.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.32 V (10.97%)10.7 V2.17 V (18.1%)59.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.04 V (8.71%)11.0 V1.72 V (14.36%)47.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.83 V (6.91%)11.2 V1.37 V (11.39%)37.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.66 V (5.48%)11.3 V1.08 V (9.03%)29.6 WDrop/Amp High
250 kcmil126.7 mm²255 A0.56 V (4.63%)11.4 V0.92 V (7.64%)25.0 W~ ≤5%
300 kcmil152.0 mm²285 A0.46 V (3.86%)11.5 V0.76 V (6.37%)20.9 W~ ≤5%
350 kcmil177.3 mm²310 A0.4 V (3.31%)11.6 V0.66 V (5.46%)17.9 W~ ≤5%
400 kcmil202.7 mm²335 A0.35 V (2.9%)11.7 V0.57 V (4.78%)15.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.28 V (2.32%)11.7 V0.46 V (3.82%)12.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.23 V (1.93%)11.8 V0.38 V (3.19%)10.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.19 V (1.54%)11.8 V0.31 V (2.55%)8.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (1.16%)11.9 V0.23 V (1.91%)6.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 120 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 120 feet one-way at 12V (DC), you need 400 kcmil copper wire. This produces a voltage drop of 0.35V (2.9%) and delivers 11.7V at the load.

What size aluminum wire is required for 45 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 0.31V (2.55%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.