⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 225 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.6%
Aluminum Wire (≤3% Drop)2 AWGDrop: 6.48V (2.7%)
Voltage at Load End233.8 VLoss: 6.25 V (281.0 W)
Power & Breaker (125%)10.8 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A63.5 V (26.46%)176.5 V104.75 V (43.65%)2857.6 WDrop/Amp High
12 AWG3.31 mm²20 A39.9 V (16.63%)200.1 V65.82 V (27.43%)1795.7 WDrop/Amp High
10 AWG5.26 mm²30 A25.11 V (10.46%)214.9 V41.42 V (17.26%)1130.0 WDrop/Amp High
8 AWG8.37 mm²50 A15.78 V (6.58%)224.2 V26.03 V (10.85%)710.1 WDrop/Amp High
6 AWG13.3 mm²65 A9.93 V (4.14%)230.1 V16.38 V (6.83%)446.9 W~ ≤5%
4 AWG21.15 mm²85 A6.25 V (2.6%)233.8 V10.3 V (4.29%)281.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A4.95 V (2.06%)235.0 V8.17 V (3.4%)222.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.93 V (1.64%)236.1 V6.48 V (2.7%)176.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.11 V (1.3%)236.9 V5.14 V (2.14%)140.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.47 V (1.03%)237.5 V4.07 V (1.7%)111.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.96 V (0.82%)238.0 V3.23 V (1.35%)88.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.55 V (0.65%)238.4 V2.56 V (1.07%)69.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.23 V (0.51%)238.8 V2.03 V (0.85%)55.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.04 V (0.43%)239.0 V1.72 V (0.72%)46.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.87 V (0.36%)239.1 V1.43 V (0.6%)39.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.74 V (0.31%)239.3 V1.23 V (0.51%)33.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.65 V (0.27%)239.3 V1.07 V (0.45%)29.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.52 V (0.22%)239.5 V0.86 V (0.36%)23.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.43 V (0.18%)239.6 V0.72 V (0.3%)19.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.35 V (0.14%)239.7 V0.57 V (0.24%)15.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.26 V (0.11%)239.7 V0.43 V (0.18%)11.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 225 feet one-way at 240V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 6.25V (2.6%) and delivers 233.8V at the load.

What size aluminum wire is required for 45 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 6.48V (2.7%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.