🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 350 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.78%
Aluminum Wire (≤3% Drop)1 AWGDrop: 6.92V (2.88%)
Voltage at Load End233.3 VLoss: 6.67 V (520.0 W)
Power & Breaker (125%)18.71 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A85.55 V (35.64%)154.5 V141.11 V (58.8%)6667.8 WDrop/Amp High
12 AWG3.31 mm²20 A53.76 V (22.4%)186.2 V88.68 V (36.95%)4190.0 WDrop/Amp High
10 AWG5.26 mm²30 A33.83 V (14.1%)206.2 V55.8 V (23.25%)2636.7 WDrop/Amp High
8 AWG8.37 mm²50 A21.26 V (8.86%)218.7 V35.07 V (14.61%)1657.0 WDrop/Amp High
6 AWG13.3 mm²65 A13.38 V (5.57%)226.6 V22.07 V (9.2%)1042.8 WDrop/Amp High
4 AWG21.15 mm²85 A8.41 V (3.51%)231.6 V13.88 V (5.78%)655.7 W~ ≤5%
3 AWG26.67 mm²100 A6.67 V (2.78%)233.3 V11.01 V (4.59%)520.0 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A5.29 V (2.21%)234.7 V8.73 V (3.64%)412.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A4.2 V (1.75%)235.8 V6.92 V (2.88%)327.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A3.33 V (1.39%)236.7 V5.49 V (2.29%)259.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.64 V (1.1%)237.4 V4.35 V (1.81%)205.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.09 V (0.87%)237.9 V3.45 V (1.44%)163.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.66 V (0.69%)238.3 V2.74 V (1.14%)129.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.4 V (0.59%)238.6 V2.32 V (0.97%)109.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.17 V (0.49%)238.8 V1.93 V (0.8%)91.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.0 V (0.42%)239.0 V1.66 V (0.69%)78.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.88 V (0.37%)239.1 V1.45 V (0.6%)68.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.7 V (0.29%)239.3 V1.16 V (0.48%)54.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.59 V (0.24%)239.4 V0.97 V (0.4%)45.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.47 V (0.2%)239.5 V0.77 V (0.32%)36.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.35 V (0.15%)239.6 V0.58 V (0.24%)27.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 350 feet one-way at 240V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 6.67V (2.78%) and delivers 233.3V at the load.

What size aluminum wire is required for 45 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 6.92V (2.88%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.