🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 60 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.75%
Aluminum Wire (≤3% Drop)6 AWGDrop: 3.78V (1.82%)
Voltage at Load End204.4 VLoss: 3.64 V (284.1 W)
Power & Breaker (125%)16.21 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 60 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A14.67 V (7.05%)193.3 V24.19 V (11.63%)1143.0 WDrop/Amp High
12 AWG3.31 mm²20 A9.22 V (4.43%)198.8 V15.2 V (7.31%)718.3 WDrop/Amp High
10 AWG5.26 mm²30 A5.8 V (2.79%)202.2 V9.57 V (4.6%)452.0 WDrop/Amp High
8 AWG8.37 mm²50 A3.64 V (1.75%)204.4 V6.01 V (2.89%)284.1 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.29 V (1.1%)205.7 V3.78 V (1.82%)178.8 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.44 V (0.69%)206.6 V2.38 V (1.14%)112.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.14 V (0.55%)206.9 V1.89 V (0.91%)89.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.91 V (0.44%)207.1 V1.5 V (0.72%)70.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.72 V (0.35%)207.3 V1.19 V (0.57%)56.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.57 V (0.27%)207.4 V0.94 V (0.45%)44.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.45 V (0.22%)207.5 V0.75 V (0.36%)35.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.36 V (0.17%)207.6 V0.59 V (0.28%)28.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.28 V (0.14%)207.7 V0.47 V (0.23%)22.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.24 V (0.12%)207.8 V0.4 V (0.19%)18.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.2 V (0.1%)207.8 V0.33 V (0.16%)15.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.17 V (0.08%)207.8 V0.28 V (0.14%)13.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.15 V (0.07%)207.8 V0.25 V (0.12%)11.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.12 V (0.06%)207.9 V0.2 V (0.1%)9.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.1 V (0.05%)207.9 V0.17 V (0.08%)7.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.08 V (0.04%)207.9 V0.13 V (0.06%)6.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.06 V (0.03%)207.9 V0.1 V (0.05%)4.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 60 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 60 feet one-way at 208V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 3.64V (1.75%) and delivers 204.4V at the load.

What size aluminum wire is required for 45 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 3.78V (1.82%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.