🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 750 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.72%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 5.87V (2.82%)
Voltage at Load End202.3 VLoss: 5.65 V (440.7 W)
Power & Breaker (125%)16.21 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 750 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A183.32 V (88.13%)24.7 V302.39 V (145.38%)14288.0 WDrop/Amp High
12 AWG3.31 mm²20 A115.2 V (55.38%)92.8 V190.02 V (91.36%)8978.6 WDrop/Amp High
10 AWG5.26 mm²30 A72.49 V (34.85%)135.5 V119.57 V (57.49%)5650.0 WDrop/Amp High
8 AWG8.37 mm²50 A45.56 V (21.9%)162.4 V75.14 V (36.13%)3550.7 WDrop/Amp High
6 AWG13.3 mm²65 A28.67 V (13.78%)179.3 V47.29 V (22.74%)2234.5 WDrop/Amp High
4 AWG21.15 mm²85 A18.03 V (8.67%)190.0 V29.74 V (14.3%)1405.2 WDrop/Amp High
3 AWG26.67 mm²100 A14.3 V (6.87%)193.7 V23.58 V (11.34%)1114.3 WDrop/Amp High
2 AWG33.62 mm²115 A11.34 V (5.45%)196.7 V18.71 V (8.99%)884.0 WDrop/Amp High
1 AWG42.41 mm²130 A8.99 V (4.32%)199.0 V14.83 V (7.13%)700.8 W~ ≤5%
1/0 AWG53.49 mm²150 A7.13 V (3.43%)200.9 V11.76 V (5.65%)555.6 W~ ≤5%
2/0 AWG67.43 mm²175 A5.65 V (2.72%)202.3 V9.33 V (4.48%)440.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.49 V (2.16%)203.5 V7.4 V (3.56%)349.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.56 V (1.71%)204.4 V5.87 V (2.82%)277.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.01 V (1.45%)205.0 V4.96 V (2.39%)234.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.51 V (1.21%)205.5 V4.14 V (1.99%)195.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.15 V (1.03%)205.8 V3.55 V (1.71%)167.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.88 V (0.9%)206.1 V3.1 V (1.49%)146.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.5 V (0.72%)206.5 V2.48 V (1.19%)117.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.25 V (0.6%)206.7 V2.07 V (0.99%)97.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.0 V (0.48%)207.0 V1.66 V (0.8%)78.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.75 V (0.36%)207.2 V1.24 V (0.6%)58.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 750 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 750 feet one-way at 208V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 5.65V (2.72%) and delivers 202.3V at the load.

What size aluminum wire is required for 45 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 5.87V (2.82%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.