⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 125 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.8%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.07V (0.99%)
Voltage at Load End206.3 VLoss: 1.67 V (1303.5 W)
Power & Breaker (125%)162.12 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 125 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A305.53 V (146.89%)0.0 V503.98 V (242.3%)238134.2 WDrop/Amp High
12 AWG3.31 mm²20 A191.99 V (92.3%)16.0 V316.7 V (152.26%)149643.2 WDrop/Amp High
10 AWG5.26 mm²30 A120.82 V (58.08%)87.2 V199.29 V (95.81%)94167.1 WDrop/Amp High
8 AWG8.37 mm²50 A75.93 V (36.5%)132.1 V125.24 V (60.21%)59177.9 WDrop/Amp High
6 AWG13.3 mm²65 A47.78 V (22.97%)160.2 V78.82 V (37.89%)37242.0 WDrop/Amp High
4 AWG21.15 mm²85 A30.05 V (14.45%)178.0 V49.56 V (23.83%)23419.3 WDrop/Amp High
3 AWG26.67 mm²100 A23.83 V (11.46%)184.2 V39.31 V (18.9%)18572.1 WDrop/Amp High
2 AWG33.62 mm²115 A18.9 V (9.09%)189.1 V31.18 V (14.99%)14732.9 WDrop/Amp High
1 AWG42.41 mm²130 A14.98 V (7.2%)193.0 V24.72 V (11.88%)11679.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.88 V (5.71%)196.1 V19.6 V (9.42%)9260.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.42 V (4.53%)198.6 V15.55 V (7.47%)7345.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.48 V (3.59%)200.5 V12.33 V (5.93%)5826.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.93 V (2.85%)202.1 V9.78 V (4.7%)4620.5 WDrop/Amp High
250 kcmil126.7 mm²255 A5.02 V (2.41%)203.0 V8.27 V (3.98%)3909.4 WDrop/Amp High
300 kcmil152.0 mm²285 A4.18 V (2.01%)203.8 V6.9 V (3.32%)3258.7 WDrop/Amp High
350 kcmil177.3 mm²310 A3.58 V (1.72%)204.4 V5.91 V (2.84%)2793.7 WDrop/Amp High
400 kcmil202.7 mm²335 A3.14 V (1.51%)204.9 V5.17 V (2.49%)2443.6 WDrop/Amp High
500 kcmil253.4 mm²380 A2.51 V (1.21%)205.5 V4.14 V (1.99%)1954.7 WDrop/Amp High
600 kcmil304.0 mm²420 A2.09 V (1.01%)205.9 V3.45 V (1.66%)1629.3 WDrop/Amp High
750 kcmil380.0 mm²475 A1.67 V (0.8%)206.3 V2.76 V (1.33%)1303.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.25 V (0.6%)206.7 V2.07 V (0.99%)977.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 125 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 125 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.67V (0.8%) and delivers 206.3V at the load.

What size aluminum wire is required for 450 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.07V (0.99%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.