🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 20 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.13%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.33V (0.16%)
Voltage at Load End207.7 VLoss: 0.27 V (208.6 W)
Power & Breaker (125%)162.12 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 20 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A48.88 V (23.5%)159.1 V80.64 V (38.77%)38101.5 WDrop/Amp High
12 AWG3.31 mm²20 A30.72 V (14.77%)177.3 V50.67 V (24.36%)23942.9 WDrop/Amp High
10 AWG5.26 mm²30 A19.33 V (9.29%)188.7 V31.89 V (15.33%)15066.7 WDrop/Amp High
8 AWG8.37 mm²50 A12.15 V (5.84%)195.9 V20.04 V (9.63%)9468.5 WDrop/Amp High
6 AWG13.3 mm²65 A7.65 V (3.68%)200.4 V12.61 V (6.06%)5958.7 WDrop/Amp High
4 AWG21.15 mm²85 A4.81 V (2.31%)203.2 V7.93 V (3.81%)3747.1 WDrop/Amp High
3 AWG26.67 mm²100 A3.81 V (1.83%)204.2 V6.29 V (3.02%)2971.5 WDrop/Amp High
2 AWG33.62 mm²115 A3.02 V (1.45%)205.0 V4.99 V (2.4%)2357.3 WDrop/Amp High
1 AWG42.41 mm²130 A2.4 V (1.15%)205.6 V3.95 V (1.9%)1868.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.9 V (0.91%)206.1 V3.14 V (1.51%)1481.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.51 V (0.72%)206.5 V2.49 V (1.2%)1175.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.2 V (0.58%)206.8 V1.97 V (0.95%)932.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.95 V (0.46%)207.1 V1.56 V (0.75%)739.3 WDrop/Amp High
250 kcmil126.7 mm²255 A0.8 V (0.39%)207.2 V1.32 V (0.64%)625.5 WDrop/Amp High
300 kcmil152.0 mm²285 A0.67 V (0.32%)207.3 V1.1 V (0.53%)521.4 WDrop/Amp High
350 kcmil177.3 mm²310 A0.57 V (0.28%)207.4 V0.95 V (0.45%)447.0 WDrop/Amp High
400 kcmil202.7 mm²335 A0.5 V (0.24%)207.5 V0.83 V (0.4%)391.0 WDrop/Amp High
500 kcmil253.4 mm²380 A0.4 V (0.19%)207.6 V0.66 V (0.32%)312.8 WDrop/Amp High
600 kcmil304.0 mm²420 A0.33 V (0.16%)207.7 V0.55 V (0.27%)260.7 WDrop/Amp High
750 kcmil380.0 mm²475 A0.27 V (0.13%)207.7 V0.44 V (0.21%)208.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.2 V (0.1%)207.8 V0.33 V (0.16%)156.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 20 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 20 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.27V (0.13%) and delivers 207.7V at the load.

What size aluminum wire is required for 450 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.33V (0.16%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.