🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 100 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.64%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.66V (0.8%)
Voltage at Load End206.7 VLoss: 1.34 V (1042.8 W)
Power & Breaker (125%)162.12 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 100 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A244.42 V (117.51%)0.0 V403.18 V (193.84%)190507.3 WDrop/Amp High
12 AWG3.31 mm²20 A153.59 V (73.84%)54.4 V253.36 V (121.81%)119714.6 WDrop/Amp High
10 AWG5.26 mm²30 A96.65 V (46.47%)111.3 V159.43 V (76.65%)75333.7 WDrop/Amp High
8 AWG8.37 mm²50 A60.74 V (29.2%)147.3 V100.19 V (48.17%)47342.3 WDrop/Amp High
6 AWG13.3 mm²65 A38.23 V (18.38%)169.8 V63.05 V (30.31%)29793.6 WDrop/Amp High
4 AWG21.15 mm²85 A24.04 V (11.56%)184.0 V39.65 V (19.06%)18735.5 WDrop/Amp High
3 AWG26.67 mm²100 A19.06 V (9.16%)188.9 V31.44 V (15.12%)14857.7 WDrop/Amp High
2 AWG33.62 mm²115 A15.12 V (7.27%)192.9 V24.94 V (11.99%)11786.3 WDrop/Amp High
1 AWG42.41 mm²130 A11.99 V (5.76%)196.0 V19.77 V (9.51%)9343.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.5 V (4.57%)198.5 V15.68 V (7.54%)7408.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.54 V (3.62%)200.5 V12.44 V (5.98%)5876.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.98 V (2.88%)202.0 V9.86 V (4.74%)4661.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.74 V (2.28%)203.3 V7.82 V (3.76%)3696.4 WDrop/Amp High
250 kcmil126.7 mm²255 A4.01 V (1.93%)204.0 V6.62 V (3.18%)3127.5 WDrop/Amp High
300 kcmil152.0 mm²285 A3.34 V (1.61%)204.7 V5.52 V (2.65%)2606.9 WDrop/Amp High
350 kcmil177.3 mm²310 A2.87 V (1.38%)205.1 V4.73 V (2.27%)2234.9 WDrop/Amp High
400 kcmil202.7 mm²335 A2.51 V (1.21%)205.5 V4.14 V (1.99%)1954.9 WDrop/Amp High
500 kcmil253.4 mm²380 A2.01 V (0.96%)206.0 V3.31 V (1.59%)1563.8 WDrop/Amp High
600 kcmil304.0 mm²420 A1.67 V (0.8%)206.3 V2.76 V (1.33%)1303.5 WDrop/Amp High
750 kcmil380.0 mm²475 A1.34 V (0.64%)206.7 V2.21 V (1.06%)1042.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.0 V (0.48%)207.0 V1.66 V (0.8%)782.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 100 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 100 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.34V (0.64%) and delivers 206.7V at the load.

What size aluminum wire is required for 450 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.66V (0.8%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.