⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 175 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.25%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.34V (2.79%)
Voltage at Load End117.3 VLoss: 2.7 V (1216.6 W)
Power & Breaker (125%)54.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 175 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A493.91 V (411.59%)0.0 V814.72 V (678.93%)222258.5 WDrop/Amp High
12 AWG3.31 mm²20 A310.37 V (258.64%)0.0 V511.97 V (426.64%)139667.0 WDrop/Amp High
10 AWG5.26 mm²30 A195.31 V (162.76%)0.0 V322.17 V (268.47%)87889.3 WDrop/Amp High
8 AWG8.37 mm²50 A122.74 V (102.28%)0.0 V202.46 V (168.72%)55232.7 WDrop/Amp High
6 AWG13.3 mm²65 A77.24 V (64.37%)42.8 V127.41 V (106.18%)34759.2 WDrop/Amp High
4 AWG21.15 mm²85 A48.57 V (40.48%)71.4 V80.12 V (66.77%)21858.1 WDrop/Amp High
3 AWG26.67 mm²100 A38.52 V (32.1%)81.5 V63.54 V (52.95%)17334.0 WDrop/Amp High
2 AWG33.62 mm²115 A30.56 V (25.46%)89.4 V50.4 V (42.0%)13750.7 WDrop/Amp High
1 AWG42.41 mm²130 A24.22 V (20.19%)95.8 V39.96 V (33.3%)10900.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A19.21 V (16.0%)100.8 V31.68 V (26.4%)8642.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A15.24 V (12.7%)104.8 V25.13 V (20.94%)6856.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.08 V (10.07%)107.9 V19.93 V (16.61%)5438.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.58 V (7.99%)110.4 V15.81 V (13.17%)4312.5 WDrop/Amp High
250 kcmil126.7 mm²255 A8.11 V (6.76%)111.9 V13.37 V (11.15%)3648.8 WDrop/Amp High
300 kcmil152.0 mm²285 A6.76 V (5.63%)113.2 V11.15 V (9.29%)3041.4 WDrop/Amp High
350 kcmil177.3 mm²310 A5.79 V (4.83%)114.2 V9.56 V (7.96%)2607.4 WDrop/Amp High
400 kcmil202.7 mm²335 A5.07 V (4.22%)114.9 V8.36 V (6.97%)2280.7 WDrop/Amp High
500 kcmil253.4 mm²380 A4.05 V (3.38%)115.9 V6.69 V (5.57%)1824.4 WDrop/Amp High
600 kcmil304.0 mm²420 A3.38 V (2.82%)116.6 V5.57 V (4.65%)1520.7 WDrop/Amp High
750 kcmil380.0 mm²475 A2.7 V (2.25%)117.3 V4.46 V (3.72%)1216.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.03 V (1.69%)118.0 V3.34 V (2.79%)912.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 175 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 175 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.7V (2.25%) and delivers 117.3V at the load.

What size aluminum wire is required for 450 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.34V (2.79%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.