🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 120 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.54%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.29V (1.91%)
Voltage at Load End118.1 VLoss: 1.85 V (834.2 W)
Power & Breaker (125%)54.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 120 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A338.68 V (282.23%)0.0 V558.66 V (465.55%)152405.9 WDrop/Amp High
12 AWG3.31 mm²20 A212.83 V (177.35%)0.0 V351.06 V (292.55%)95771.7 WDrop/Amp High
10 AWG5.26 mm²30 A133.93 V (111.61%)0.0 V220.92 V (184.1%)60267.0 WDrop/Amp High
8 AWG8.37 mm²50 A84.16 V (70.14%)35.8 V138.83 V (115.69%)37873.9 WDrop/Amp High
6 AWG13.3 mm²65 A52.97 V (44.14%)67.0 V87.37 V (72.81%)23834.9 WDrop/Amp High
4 AWG21.15 mm²85 A33.31 V (27.76%)86.7 V54.94 V (45.78%)14988.4 WDrop/Amp High
3 AWG26.67 mm²100 A26.41 V (22.01%)93.6 V43.57 V (36.31%)11886.2 WDrop/Amp High
2 AWG33.62 mm²115 A20.95 V (17.46%)99.0 V34.56 V (28.8%)9429.0 WDrop/Amp High
1 AWG42.41 mm²130 A16.61 V (13.84%)103.4 V27.4 V (22.83%)7474.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.17 V (10.97%)106.8 V21.72 V (18.1%)5926.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.45 V (8.71%)109.6 V17.23 V (14.36%)4701.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.29 V (6.91%)111.7 V13.67 V (11.39%)3729.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.57 V (5.48%)113.4 V10.84 V (9.03%)2957.1 WDrop/Amp High
250 kcmil126.7 mm²255 A5.56 V (4.63%)114.4 V9.17 V (7.64%)2502.0 WDrop/Amp High
300 kcmil152.0 mm²285 A4.63 V (3.86%)115.4 V7.64 V (6.37%)2085.6 WDrop/Amp High
350 kcmil177.3 mm²310 A3.97 V (3.31%)116.0 V6.55 V (5.46%)1788.0 WDrop/Amp High
400 kcmil202.7 mm²335 A3.48 V (2.9%)116.5 V5.73 V (4.78%)1563.9 WDrop/Amp High
500 kcmil253.4 mm²380 A2.78 V (2.32%)117.2 V4.59 V (3.82%)1251.0 WDrop/Amp High
600 kcmil304.0 mm²420 A2.32 V (1.93%)117.7 V3.82 V (3.19%)1042.8 WDrop/Amp High
750 kcmil380.0 mm²475 A1.85 V (1.54%)118.1 V3.06 V (2.55%)834.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.39 V (1.16%)118.6 V2.29 V (1.91%)625.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 120 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 120 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.85V (1.54%) and delivers 118.1V at the load.

What size aluminum wire is required for 450 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.29V (1.91%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.