🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 500 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.39%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.28V (1.72%)
Voltage at Load End473.3 VLoss: 6.69 V (5213.9 W)
Power & Breaker (125%)374.12 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 500 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1222.11 V (254.61%)0.0 V2015.9 V (419.98%)952536.6 WDrop/Amp High
12 AWG3.31 mm²20 A767.97 V (159.99%)0.0 V1266.79 V (263.91%)598572.9 WDrop/Amp High
10 AWG5.26 mm²30 A483.27 V (100.68%)0.0 V797.16 V (166.08%)376668.5 WDrop/Amp High
8 AWG8.37 mm²50 A303.7 V (63.27%)176.3 V500.96 V (104.37%)236711.6 WDrop/Amp High
6 AWG13.3 mm²65 A191.13 V (39.82%)288.9 V315.27 V (65.68%)148968.1 WDrop/Amp High
4 AWG21.15 mm²85 A120.19 V (25.04%)359.8 V198.25 V (41.3%)93677.4 WDrop/Amp High
3 AWG26.67 mm²100 A95.31 V (19.86%)384.7 V157.22 V (32.75%)74288.6 WDrop/Amp High
2 AWG33.62 mm²115 A75.61 V (15.75%)404.4 V124.72 V (25.98%)58931.5 WDrop/Amp High
1 AWG42.41 mm²130 A59.94 V (12.49%)420.1 V98.87 V (20.6%)46717.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A47.52 V (9.9%)432.5 V78.39 V (16.33%)37040.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A37.7 V (7.85%)442.3 V62.18 V (12.96%)29382.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A29.9 V (6.23%)450.1 V49.32 V (10.28%)23306.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A23.71 V (4.94%)456.3 V39.11 V (8.15%)18482.1 WDrop/Amp High
250 kcmil126.7 mm²255 A20.06 V (4.18%)459.9 V33.09 V (6.89%)15637.5 WDrop/Amp High
300 kcmil152.0 mm²285 A16.72 V (3.48%)463.3 V27.59 V (5.75%)13034.7 WDrop/Amp High
350 kcmil177.3 mm²310 A14.34 V (2.99%)465.7 V23.65 V (4.93%)11174.7 WDrop/Amp High
400 kcmil202.7 mm²335 A12.54 V (2.61%)467.5 V20.69 V (4.31%)9774.4 WDrop/Amp High
500 kcmil253.4 mm²380 A10.03 V (2.09%)470.0 V16.55 V (3.45%)7818.8 WDrop/Amp High
600 kcmil304.0 mm²420 A8.36 V (1.74%)471.6 V13.79 V (2.87%)6517.4 WDrop/Amp High
750 kcmil380.0 mm²475 A6.69 V (1.39%)473.3 V11.03 V (2.3%)5213.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A5.02 V (1.05%)475.0 V8.28 V (1.72%)3910.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 500 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 500 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 6.69V (1.39%) and delivers 473.3V at the load.

What size aluminum wire is required for 450 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.28V (1.72%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.