⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 50 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.14%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.83V (0.17%)
Voltage at Load End479.3 VLoss: 0.67 V (521.4 W)
Power & Breaker (125%)374.12 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 50 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A122.21 V (25.46%)357.8 V201.59 V (42.0%)95253.7 WDrop/Amp High
12 AWG3.31 mm²20 A76.8 V (16.0%)403.2 V126.68 V (26.39%)59857.3 WDrop/Amp High
10 AWG5.26 mm²30 A48.33 V (10.07%)431.7 V79.72 V (16.61%)37666.8 WDrop/Amp High
8 AWG8.37 mm²50 A30.37 V (6.33%)449.6 V50.1 V (10.44%)23671.2 WDrop/Amp High
6 AWG13.3 mm²65 A19.11 V (3.98%)460.9 V31.53 V (6.57%)14896.8 WDrop/Amp High
4 AWG21.15 mm²85 A12.02 V (2.5%)468.0 V19.83 V (4.13%)9367.7 WDrop/Amp High
3 AWG26.67 mm²100 A9.53 V (1.99%)470.5 V15.72 V (3.28%)7428.9 WDrop/Amp High
2 AWG33.62 mm²115 A7.56 V (1.58%)472.4 V12.47 V (2.6%)5893.1 WDrop/Amp High
1 AWG42.41 mm²130 A5.99 V (1.25%)474.0 V9.89 V (2.06%)4671.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.75 V (0.99%)475.2 V7.84 V (1.63%)3704.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.77 V (0.79%)476.2 V6.22 V (1.3%)2938.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.99 V (0.62%)477.0 V4.93 V (1.03%)2330.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.37 V (0.49%)477.6 V3.91 V (0.81%)1848.2 WDrop/Amp High
250 kcmil126.7 mm²255 A2.01 V (0.42%)478.0 V3.31 V (0.69%)1563.8 WDrop/Amp High
300 kcmil152.0 mm²285 A1.67 V (0.35%)478.3 V2.76 V (0.57%)1303.5 WDrop/Amp High
350 kcmil177.3 mm²310 A1.43 V (0.3%)478.6 V2.36 V (0.49%)1117.5 WDrop/Amp High
400 kcmil202.7 mm²335 A1.25 V (0.26%)478.7 V2.07 V (0.43%)977.4 WDrop/Amp High
500 kcmil253.4 mm²380 A1.0 V (0.21%)479.0 V1.65 V (0.34%)781.9 WDrop/Amp High
600 kcmil304.0 mm²420 A0.84 V (0.17%)479.2 V1.38 V (0.29%)651.7 WDrop/Amp High
750 kcmil380.0 mm²475 A0.67 V (0.14%)479.3 V1.1 V (0.23%)521.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.5 V (0.1%)479.5 V0.83 V (0.17%)391.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 50 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 50 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.67V (0.14%) and delivers 479.3V at the load.

What size aluminum wire is required for 450 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.83V (0.17%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.