🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 20 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.27%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.4V (0.34%)
Voltage at Load End119.7 VLoss: 0.33 V (154.9 W)
Power & Breaker (125%)57.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 20 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A59.58 V (49.65%)60.4 V98.28 V (81.9%)28301.7 WDrop/Amp High
12 AWG3.31 mm²20 A37.44 V (31.2%)82.6 V61.76 V (51.47%)17784.8 WDrop/Amp High
10 AWG5.26 mm²30 A23.56 V (19.63%)96.4 V38.86 V (32.39%)11191.5 WDrop/Amp High
8 AWG8.37 mm²50 A14.81 V (12.34%)105.2 V24.42 V (20.35%)7033.2 WDrop/Amp High
6 AWG13.3 mm²65 A9.32 V (7.77%)110.7 V15.37 V (12.81%)4426.1 WDrop/Amp High
4 AWG21.15 mm²85 A5.86 V (4.88%)114.1 V9.67 V (8.05%)2783.3 WDrop/Amp High
3 AWG26.67 mm²100 A4.65 V (3.87%)115.4 V7.67 V (6.39%)2207.3 WDrop/Amp High
2 AWG33.62 mm²115 A3.69 V (3.07%)116.3 V6.08 V (5.07%)1751.0 WDrop/Amp High
1 AWG42.41 mm²130 A2.92 V (2.44%)117.1 V4.82 V (4.02%)1388.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.32 V (1.93%)117.7 V3.82 V (3.18%)1100.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.84 V (1.53%)118.2 V3.03 V (2.53%)873.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.46 V (1.21%)118.5 V2.4 V (2.0%)692.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.16 V (0.96%)118.8 V1.91 V (1.59%)549.1 WDrop/Amp High
250 kcmil126.7 mm²255 A0.98 V (0.82%)119.0 V1.61 V (1.34%)464.6 WDrop/Amp High
300 kcmil152.0 mm²285 A0.82 V (0.68%)119.2 V1.34 V (1.12%)387.3 WDrop/Amp High
350 kcmil177.3 mm²310 A0.7 V (0.58%)119.3 V1.15 V (0.96%)332.0 WDrop/Amp High
400 kcmil202.7 mm²335 A0.61 V (0.51%)119.4 V1.01 V (0.84%)290.4 WDrop/Amp High
500 kcmil253.4 mm²380 A0.49 V (0.41%)119.5 V0.81 V (0.67%)232.3 WDrop/Amp High
600 kcmil304.0 mm²420 A0.41 V (0.34%)119.6 V0.67 V (0.56%)193.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.33 V (0.27%)119.7 V0.54 V (0.45%)154.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.24 V (0.2%)119.8 V0.4 V (0.34%)116.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 20 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 20 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.33V (0.27%) and delivers 119.7V at the load.

What size aluminum wire is required for 475 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.4V (0.34%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.