🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 120 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.63%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.42V (2.02%)
Voltage at Load End118.0 VLoss: 1.96 V (929.5 W)
Power & Breaker (125%)57.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 120 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A357.5 V (297.91%)0.0 V589.7 V (491.42%)169810.2 WDrop/Amp High
12 AWG3.31 mm²20 A224.65 V (187.21%)0.0 V370.57 V (308.81%)106708.5 WDrop/Amp High
10 AWG5.26 mm²30 A141.37 V (117.81%)0.0 V233.19 V (194.32%)67149.3 WDrop/Amp High
8 AWG8.37 mm²50 A88.84 V (74.03%)31.2 V146.54 V (122.12%)42199.0 WDrop/Amp High
6 AWG13.3 mm²65 A55.91 V (46.59%)64.1 V92.22 V (76.85%)26556.8 WDrop/Amp High
4 AWG21.15 mm²85 A35.16 V (29.3%)84.8 V57.99 V (48.33%)16700.0 WDrop/Amp High
3 AWG26.67 mm²100 A27.88 V (23.23%)92.1 V45.99 V (38.33%)13243.5 WDrop/Amp High
2 AWG33.62 mm²115 A22.12 V (18.43%)97.9 V36.48 V (30.4%)10505.8 WDrop/Amp High
1 AWG42.41 mm²130 A17.53 V (14.61%)102.5 V28.92 V (24.1%)8328.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.9 V (11.58%)106.1 V22.93 V (19.11%)6603.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.03 V (9.19%)109.0 V18.19 V (15.16%)5238.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.75 V (7.29%)111.3 V14.43 V (12.02%)4154.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.94 V (5.78%)113.1 V11.44 V (9.53%)3294.8 WDrop/Amp High
250 kcmil126.7 mm²255 A5.87 V (4.89%)114.1 V9.68 V (8.07%)2787.7 WDrop/Amp High
300 kcmil152.0 mm²285 A4.89 V (4.08%)115.1 V8.07 V (6.72%)2323.7 WDrop/Amp High
350 kcmil177.3 mm²310 A4.19 V (3.49%)115.8 V6.92 V (5.77%)1992.1 WDrop/Amp High
400 kcmil202.7 mm²335 A3.67 V (3.06%)116.3 V6.05 V (5.04%)1742.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.93 V (2.45%)117.1 V4.84 V (4.03%)1393.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.45 V (2.04%)117.6 V4.03 V (3.36%)1161.9 WDrop/Amp High
750 kcmil380.0 mm²475 A1.96 V (1.63%)118.0 V3.23 V (2.69%)929.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.47 V (1.22%)118.5 V2.42 V (2.02%)697.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 120 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 120 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.96V (1.63%) and delivers 118.0V at the load.

What size aluminum wire is required for 475 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.42V (2.02%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.