🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 175 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)7× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.72V (30.97%)
Voltage at Load End11.7 VLoss: 0.32 V (160.9 W)
Power & Breaker (125%)6.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 175 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A548.79 V (4573.22%)0.0 V905.24 V (7543.68%)274393.3 WDrop/Amp High
12 AWG3.31 mm²20 A344.86 V (2873.81%)0.0 V568.85 V (4740.44%)172428.4 WDrop/Amp High
10 AWG5.26 mm²30 A217.01 V (1808.42%)0.0 V357.97 V (2983.05%)108505.3 WDrop/Amp High
8 AWG8.37 mm²50 A136.38 V (1136.48%)0.0 V224.96 V (1874.65%)68188.5 WDrop/Amp High
6 AWG13.3 mm²65 A85.83 V (715.21%)0.0 V141.57 V (1179.76%)42912.6 WDrop/Amp High
4 AWG21.15 mm²85 A53.97 V (449.75%)0.0 V89.03 V (741.88%)26985.2 WDrop/Amp High
3 AWG26.67 mm²100 A42.8 V (356.67%)0.0 V70.6 V (588.33%)21400.0 WDrop/Amp High
2 AWG33.62 mm²115 A33.95 V (282.94%)0.0 V56.01 V (466.71%)16976.1 WDrop/Amp High
1 AWG42.41 mm²130 A26.92 V (224.29%)0.0 V44.4 V (369.98%)13457.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A21.34 V (177.83%)0.0 V35.2 V (293.34%)10670.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.93 V (141.07%)0.0 V27.92 V (232.7%)8464.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.43 V (111.9%)0.0 V22.15 V (184.58%)6713.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.65 V (88.73%)1.4 V17.56 V (146.37%)5324.0 WDrop/Amp High
250 kcmil126.7 mm²255 A9.01 V (75.08%)3.0 V14.86 V (123.84%)4504.6 WDrop/Amp High
300 kcmil152.0 mm²285 A7.51 V (62.58%)4.5 V12.39 V (103.23%)3754.9 WDrop/Amp High
350 kcmil177.3 mm²310 A6.44 V (53.65%)5.6 V10.62 V (88.5%)3219.1 WDrop/Amp High
400 kcmil202.7 mm²335 A5.63 V (46.93%)6.4 V9.29 V (77.41%)2815.7 WDrop/Amp High
500 kcmil253.4 mm²380 A4.5 V (37.54%)7.5 V7.43 V (61.92%)2252.3 WDrop/Amp High
600 kcmil304.0 mm²420 A3.75 V (31.29%)8.2 V6.19 V (51.61%)1877.4 WDrop/Amp High
750 kcmil380.0 mm²475 A3.0 V (25.03%)9.0 V4.96 V (41.29%)1501.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.25 V (18.77%)9.7 V3.72 V (30.97%)1126.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 175 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 175 feet one-way at 12V (DC), you need 7× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.32V (2.68%) and delivers 11.7V at the load.

What size aluminum wire is required for 500 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.72V (30.97%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.