🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 40 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.15%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.85V (7.08%)
Voltage at Load End11.7 VLoss: 0.26 V (128.8 W)
Power & Breaker (125%)6.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 40 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A125.44 V (1045.31%)0.0 V206.91 V (1724.27%)62718.5 WDrop/Amp High
12 AWG3.31 mm²20 A78.82 V (656.87%)0.0 V130.02 V (1083.53%)39412.2 WDrop/Amp High
10 AWG5.26 mm²30 A49.6 V (413.35%)0.0 V81.82 V (681.84%)24801.2 WDrop/Amp High
8 AWG8.37 mm²50 A31.17 V (259.77%)0.0 V51.42 V (428.49%)15585.9 WDrop/Amp High
6 AWG13.3 mm²65 A19.62 V (163.48%)0.0 V32.36 V (269.66%)9808.6 WDrop/Amp High
4 AWG21.15 mm²85 A12.34 V (102.8%)0.0 V20.35 V (169.57%)6168.1 WDrop/Amp High
3 AWG26.67 mm²100 A9.78 V (81.52%)2.2 V16.14 V (134.48%)4891.4 WDrop/Amp High
2 AWG33.62 mm²115 A7.76 V (64.67%)4.2 V12.8 V (106.68%)3880.3 WDrop/Amp High
1 AWG42.41 mm²130 A6.15 V (51.27%)5.8 V10.15 V (84.57%)3076.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.88 V (40.65%)7.1 V8.05 V (67.05%)2438.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.87 V (32.24%)8.1 V6.38 V (53.19%)1934.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.07 V (25.58%)8.9 V5.06 V (42.19%)1534.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.43 V (20.28%)9.6 V4.01 V (33.46%)1216.9 WDrop/Amp High
250 kcmil126.7 mm²255 A2.06 V (17.16%)9.9 V3.4 V (28.31%)1029.6 WDrop/Amp High
300 kcmil152.0 mm²285 A1.72 V (14.3%)10.3 V2.83 V (23.6%)858.3 WDrop/Amp High
350 kcmil177.3 mm²310 A1.47 V (12.26%)10.5 V2.43 V (20.23%)735.8 WDrop/Amp High
400 kcmil202.7 mm²335 A1.29 V (10.73%)10.7 V2.12 V (17.69%)643.6 WDrop/Amp High
500 kcmil253.4 mm²380 A1.03 V (8.58%)11.0 V1.7 V (14.15%)514.8 WDrop/Amp High
600 kcmil304.0 mm²420 A0.86 V (7.15%)11.1 V1.42 V (11.8%)429.1 WDrop/Amp High
750 kcmil380.0 mm²475 A0.69 V (5.72%)11.3 V1.13 V (9.44%)343.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.51 V (4.29%)11.5 V0.85 V (7.08%)257.5 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 40 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 40 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.26V (2.15%) and delivers 11.7V at the load.

What size aluminum wire is required for 500 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.85V (7.08%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.