⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 20 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 0.11%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.42V (0.18%)
Voltage at Load End239.7 VLoss: 0.26 V (128.7 W)
Power & Breaker (125%)120.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 20 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A62.72 V (26.13%)177.3 V103.46 V (43.11%)31359.2 WDrop/Amp High
12 AWG3.31 mm²20 A39.41 V (16.42%)200.6 V65.01 V (27.09%)19706.1 WDrop/Amp High
10 AWG5.26 mm²30 A24.8 V (10.33%)215.2 V40.91 V (17.05%)12400.6 WDrop/Amp High
8 AWG8.37 mm²50 A15.59 V (6.49%)224.4 V25.71 V (10.71%)7793.0 WDrop/Amp High
6 AWG13.3 mm²65 A9.81 V (4.09%)230.2 V16.18 V (6.74%)4904.3 WDrop/Amp High
4 AWG21.15 mm²85 A6.17 V (2.57%)233.8 V10.17 V (4.24%)3084.0 WDrop/Amp High
3 AWG26.67 mm²100 A4.89 V (2.04%)235.1 V8.07 V (3.36%)2445.7 WDrop/Amp High
2 AWG33.62 mm²115 A3.88 V (1.62%)236.1 V6.4 V (2.67%)1940.1 WDrop/Amp High
1 AWG42.41 mm²130 A3.08 V (1.28%)236.9 V5.07 V (2.11%)1538.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.44 V (1.02%)237.6 V4.02 V (1.68%)1219.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.93 V (0.81%)238.1 V3.19 V (1.33%)967.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.53 V (0.64%)238.5 V2.53 V (1.05%)767.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.22 V (0.51%)238.8 V2.01 V (0.84%)608.5 WDrop/Amp High
250 kcmil126.7 mm²255 A1.03 V (0.43%)239.0 V1.7 V (0.71%)514.8 WDrop/Amp High
300 kcmil152.0 mm²285 A0.86 V (0.36%)239.1 V1.42 V (0.59%)429.1 WDrop/Amp High
350 kcmil177.3 mm²310 A0.74 V (0.31%)239.3 V1.21 V (0.51%)367.9 WDrop/Amp High
400 kcmil202.7 mm²335 A0.64 V (0.27%)239.4 V1.06 V (0.44%)321.8 WDrop/Amp High
500 kcmil253.4 mm²380 A0.51 V (0.21%)239.5 V0.85 V (0.35%)257.4 WDrop/Amp High
600 kcmil304.0 mm²420 A0.43 V (0.18%)239.6 V0.71 V (0.29%)214.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.34 V (0.14%)239.7 V0.57 V (0.24%)171.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.26 V (0.11%)239.7 V0.42 V (0.18%)128.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 20 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 20 feet one-way at 240V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 0.26V (0.11%) and delivers 239.7V at the load.

What size aluminum wire is required for 500 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.42V (0.18%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.