🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 120 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 0.64%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.55V (1.06%)
Voltage at Load End238.5 VLoss: 1.54 V (772.4 W)
Power & Breaker (125%)120.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A376.31 V (156.8%)0.0 V620.74 V (258.64%)188155.4 WDrop/Amp High
12 AWG3.31 mm²20 A236.47 V (98.53%)3.5 V390.07 V (162.53%)118236.6 WDrop/Amp High
10 AWG5.26 mm²30 A148.81 V (62.0%)91.2 V245.46 V (102.28%)74403.7 WDrop/Amp High
8 AWG8.37 mm²50 A93.52 V (38.96%)146.5 V154.26 V (64.27%)46757.8 WDrop/Amp High
6 AWG13.3 mm²65 A58.85 V (24.52%)181.1 V97.08 V (40.45%)29425.8 WDrop/Amp High
4 AWG21.15 mm²85 A37.01 V (15.42%)203.0 V61.05 V (25.44%)18504.2 WDrop/Amp High
3 AWG26.67 mm²100 A29.35 V (12.23%)210.7 V48.41 V (20.17%)14674.3 WDrop/Amp High
2 AWG33.62 mm²115 A23.28 V (9.7%)216.7 V38.4 V (16.0%)11640.8 WDrop/Amp High
1 AWG42.41 mm²130 A18.46 V (7.69%)221.5 V30.44 V (12.69%)9228.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A14.63 V (6.1%)225.4 V24.14 V (10.06%)7316.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.61 V (4.84%)228.4 V19.15 V (7.98%)5804.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.21 V (3.84%)230.8 V15.19 V (6.33%)4603.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.3 V (3.04%)232.7 V12.04 V (5.02%)3650.8 WDrop/Amp High
250 kcmil126.7 mm²255 A6.18 V (2.57%)233.8 V10.19 V (4.25%)3088.9 WDrop/Amp High
300 kcmil152.0 mm²285 A5.15 V (2.15%)234.9 V8.49 V (3.54%)2574.8 WDrop/Amp High
350 kcmil177.3 mm²310 A4.41 V (1.84%)235.6 V7.28 V (3.03%)2207.4 WDrop/Amp High
400 kcmil202.7 mm²335 A3.86 V (1.61%)236.1 V6.37 V (2.65%)1930.8 WDrop/Amp High
500 kcmil253.4 mm²380 A3.09 V (1.29%)236.9 V5.1 V (2.12%)1544.4 WDrop/Amp High
600 kcmil304.0 mm²420 A2.57 V (1.07%)237.4 V4.25 V (1.77%)1287.4 WDrop/Amp High
750 kcmil380.0 mm²475 A2.06 V (0.86%)237.9 V3.4 V (1.42%)1029.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.54 V (0.64%)238.5 V2.55 V (1.06%)772.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 120 feet one-way at 240V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 1.54V (0.64%) and delivers 238.5V at the load.

What size aluminum wire is required for 500 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.55V (1.06%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.